Solid fuel boiler Prog. no. Level Standard value
Locks other heat sources
Off | On
4102 E Off
Setpoint min 4110 E 65 °C
Temp diff on 4130 E 8 °C
Temp diff off 4131 E 4 °C
Comparative temp
Hot water sensor B3 | Hot water sensor B31 | Buffer sensor B4 | Buffer sensor
B41 | Flow temp setpoint | Setpoint min
4133 E Buffer sensor B41
Pump overrun time 4140 E 20 min
Buffer storage tank Prog. no. Level Standard value
Auto generation lock
None | With B4 | With B4 and B42/B41
4720 E With B4
Auto heat gen lock SD 4721 E 5 °C
Temp diff buffer/CH 4722 E -3 °C
Min st tank temp heat mode 4724 E - - - °C
Charging temp max 4750 E 80 °C
Recooling temp 4755 E 60 °C
Recooling HW/CHs
Off | On
4756 E Off
Recooling collector
Off | Summer | Always
4757 E Off
With solar integration
No | Yes
4783 E Yes
Temp diff on return div 4790 E 8 °C
Temp diff off return div 4791 E 4 °C
Compar temp return div
With B4 | With B41 | With B42
4795 E With B4
Optg action return diversion
Temp decrease | Temp increase
4796 E Temp increase
Full charging
Off | Heating mode | Always
4810 E Off
Full charging temp min 4811 E 8 °C
Full charging sensor
With B4 | With B42/B41
4813 E With B42/B41
Domestic water storage tank
(1)
Prog. no. Level Standard value
Forward shift charging 5011 E 60 min
Flow setpoint boost 5020 E 18 °C
Transfer boost 5021 E 10 °C
Type of charging
Recharging | Full charging | Full charging legio | Full charg 1st time day | Full
charg 1st time legio
5022 E Full charging
Switching diff 5024 E 4 °C
Charging time limitation 5030 E 120 min
Discharging protection
Off | Always | Automatically
5040 E Automatically
Charging temp max 5050 E 69 °C
Recooling temp 5055 E 80 °C
9 Settings
7658013 - 02 - 15092016 Paramount four 30 – 115 kW 65