Domestic water storage tank
(1)
Prog. no. Level Standard value
Recooling collector
Off | Summer | Always
5057 E Off
El imm heater optg mode
Substitute | Summer | Always
5060 E Substitute
El immersion heater release
24h/day | Hot water release | Time hot water
5061 E Hot water release
El immersion heater control
External thermostat | Hot water sensor
5062 E Hot water sensor
Hot water boost
Off | On
5070 E On
Excess heat draw
Off | On
5085 E On
With buffer
No | Yes
5090 E Yes
With prim contr/system pump
No | Yes
5092 E Yes
With solar integration
No | Yes
5093 E Yes
Pump speed min 5101 E 0 %
Pump speed max 5102 E 100 %
Speed Xp 5103 E 35 °C
Speed Tn 5104 E 120 s
Speed Tv 5105 E 45 s
Transfer strategy
Always | Hot water release
5130 E Always
Interm circ boost recharging 5139 E 5 °C
Intermediate circuit boost 5140 E 2 °C
Excess interm circ temp max 5141 E 2 °C
Flow setp compensation delay 5142 E 30 s
Flow setp compensation Xp 5143 E 60 °C
Flow setp compensation Tn 5144 E 30 s
Flow setp compensation Tv 5145 E 30 s
Full charging with B36
No | Yes
5146 E No
Min start temp diff Q33 5148 E -3 °C
Excess interm circ temp del 5151 E 30 s
(1) Parameters depend on the hydraulic System!
Configuration Prog. no. Level Standard value
Temps / mode CH1
Off | On
5710 C On
Temps / mode CH2
Off | On
5715 C Off
Temps / mode CH3
Off | On
5721 C Off
Hot water sensor
Hot water sensor B3 | Thermostat
5730 E Hot water sensor B3
Hot water ctrl elem Q3
No charging request | Charging pump | Diverting valve
5731 E Charging pump
Basic pos HW div valve
Last request | Central heating | Hot water
5734 E Central heating
9 Settings
66 Paramount four 30 – 115 kW 7658013 - 02 - 15092016