Communication
89
Powerware
®
9170
+
UPS User’s Guide S Rev B www.powerware.com
On-Generator: An external signal that the input power is being supplied
by a g enerator. Closure of this contact causes the UPS to change the
following parameters to preset values that are designed to optimize
performance during periods of generator instability:
Phase Lock Window and Frequency Slew Rate. These parameters
increase the rate at which the UPS tracks the input line, which causes
fewer recognized line faults during generator instability.
Frequency Glitch Count. This p arameter increases the number of bad
frequency cycles before the unit transfers to battery power. This
allows the UPS to operate smoothly during generator instability
without transferring to battery.
Maximum Delta and Line Delta. These parameters widen the
acceptable input voltage range, allowing the UPS to ignore any
transient voltage regulation problems a generator may experience
during unstable periods.
These parameters are also available to trained service personnel through
the Service Menu.
SeeFigure15onpage26andFigure21onpage31tomakethe
connection for all dedicated input signals.