The third parameter has no function when miscellaneous relay is chosen
and will not be displayed.
The fourth parameter, and fifth parameter, are set to determine the switch
points, “ON” and “OFF” for the relay. See miscellaneous function table
(P211, 221, 231) for further information.
P210, 220, 230, 240, 250 = 1 (Clock)
P213, 223, 233 – Relay Setpoint 1
Relay Setpoints are entered in Hours & Minutes (HH:MM) to set Time at
which relay will energise. Default = 00:00 (HH:MM)
P214, 224, 234 – Relay Setpoint 2
Relay Setpoints are entered in seconds to set the Time Period that the relay
will remain ‘ON’. Default = 0.00 mins.
P210, 220, 230= 2 (Totaliser)
P213, 223, 233 – Relay Setpoint 1
Relay Setpoints are entered as a factor by which the on-board totaliser
(P820) should be multiplied by to provide a relay closure. Default = 0.00
P214, 224, 234 – Relay Setpoint 2
Relay Setpoints are entered in seconds to set the Time Period that the relay
will remain ‘ON’. Default = 0.00 secs.