PULSAR MEASUREMENT
45
Vantage 3
The Vantage 3 level controller provides pump control with a complete range
of pump “duties” being available.
The Vantage 3 can measure from zero to 15m from the face of the
transducer to the surface being monitored, dependent on the transducer
used. The Vantage 3 can show level, space, or distance on the display.
The three user definable relays with individual setpoints can be programmed
to activate alarms, pump starters, or other control equipment.
The 4-20 mA output is fully programmable to provide an output relative to
level, space, or distance.
Flow
If you require to set up a flow application, then press “3” followed by
“ENTER” the message “Loading ***” will be displayed and your Ultra 3 will be
configured as a Flow 3. Confirmation that configuration has been
completed will be given by the unit type, software version and serial number
being displayed briefly on the LCD and the unit advancing to the relevant
“Quick Setup” menu. For full details on how to programme the Flow 3,
using the Quick Setup Menu, please proceed to Chapter 7 Flow. For a full
description of all features and parameters please refer to Chapter 8
Parameter Listing and Description.
Flow 3
The Flow 3 open channel flowmeter provides comprehensive flow
monitoring with data logging and control functions for a complete range of
flumes, weirs, and channels. Flow calculations to the British Standard BS3680
are available within the software together with calculations for a wide variety
of other primary elements. Also available within the unit is a customised
32-point calibration routine which also permits the flow measurement of
non - standard flumes and weirs.
The Flow 3 can measure from zero to 15 m from the transducer to the
surface being monitored, dependent on the transducer used. The Flow 3
can show details of level, space, distance, head, or flow on the display
along with a totaliser if desired. The three user-definable relays with
individual setpoints can be programmed to activate devices such as pumps,
samplers, remote totalisers or other control equipment.
The 4-20 mA output is fully programmable to provide an output relative to
level, space, distance, head, or flow.