PULSAR MEASUREMENT
171
Remote Alarm
When a Modem is connected, via the RS232 port, (Consult Pulsar or your
local distributor for further details), the following parameters are used to set
up the Ultra 3 so that when the level reaches a specific alarm point, as
determined by the setting of the relay(s) the unit will dial and connect to a
remote telephone number to provide details of the event.
P144 Call Type
This parameter determines what type of connection is made via the modem.
OPTION
DESCRIPTION
0 = Off (Default)
Remote alarm function is disabled
1 = Ring
This option initiates a connection to a remote
modem/computer which will then allow remote
communication with the unit. Please consult Pulsar or
your local distributor for further details.
2 = SMS
This option initiates a predetermined message which is
sent to the remote telephone number detailing date and
time the alarm was initiated, the site ID, alarm condition
and level at the time the alarm was initiated.
P145 Tel. No.1
This parameter is used to enter the number of ‘0’s that appear at the
beginning of the telephone number to be dialled to receive the message.
OPTION
DESCRIPTION
0= None
No ‘0’s present at the beginning of the telephone number
to be dialled.
1 = Add 0 (Default)
1 ‘0’ present at the beginning of the telephone number to
be dialled.
2= Add 00
2 ‘0’s present at the beginning of the telephone number
to be dialled.