DFM 6.1 INSTRUCTION MANUAL 
 
30 
FIELD TROUBLESHOOTING 
POSSIBLE CAUSES: 
CORRECTIVE ACTION: 
 
METER READING LOWER THAN EXPECTED 
Calibration Error 
  Review   UNITS/MODE  menu and   Pipe ID 
Lower flow rate than expected  
  Investigate pump/valves. Compare velocity 
with alternate instrument 
  Check “Cal Constant” in Special Functions 
menu. 
Improper mounting of sensor   
  Reinstall Sensor with careful application of 
Coupling Compound 
Pipe is not full   
  Remount Sensor on vertical pipe 
 
METER READING WHEN THERE IS NO FLOW 
Local electrical noise 
  Adjust Signal Cutoff in Calibration Menu 
  Ensure all Flowmeter wiring is in METAL 
conduit and sensor shield is properly 
grounded. 
  Ensure correct power input Ground 
connection (<1 ohm resistance). 
  Ensure 4-20mA Shield connected to 
Instrument Ground stud. 
Cross talk between two or more DFM 6.1 
flowmeters on same pipe   
  Refer to Synchronization instructions 
Variable Speed Drive interference 
  Follow Drive manufacturers wiring and 
Grounding instructions 
  Relocate Flowmeter electronics, Sensor and 
wiring away from VSD 
Sensor cable connections incorrect or loose 
  Refer to Connections diagram. Disconnect and 
reconnect sensor cables ensuring that cable is 
properly inserted into terminals and tightened. 
 
 
 
METER READING ERRATIC   
Sensor mounted too close to valve, pump or elbow
   
  Change sensor placement. Recommended 6-
10 diameters from elbows, and 30 diameters 
from pumps, controlling valves, orifice plates, 
nozzles or open pipe discharge