This chapter explains how to use the various functions of your IMP+. Where 
specific parameters are used, consult Parameter Guide in Chapter 5. 
Setting up Your Application 
Empty Distance 
Empty Distance (P105) is the distance from the face of the transducer to 
the material at the bottom of the vessel. 
Span 
Span (P106) is the distance from the empty level (0% full) to span (100% 
full). 
Near and Far Blanking 
Near blanking (P107) is the distance from the face of the transducer that 
the Imp will not record a level nearer than. A typical reason to increase this 
from the default value would be if you wish to ignore close in obstructions. 
Far blanking (P108) is the distance (as a percentage of empty level) beyond 
the empty level that the Imp will read, the default is plus 20% of empty level. 
If you wish to monitor further than the empty level, then increase this 
figure, so that the empty level plus the far blanking figure (as % of empty 
level) is greater than the surface being measured, within the capability of the 
transducer being used. 
Using the 4-20 mA Output 
The mA output can be used to monitor remotely what the IMP+ is showing, 
so it can be displayed remotely, integrated into a PLC, or used to generate a 
record using a chart recorder or similar.  
By default, the IMP+ will provide a 4-20 mA output that represents what is 
displayed on the Imp, but these parameters can be overwritten as follows. 
By default, the 4-20 mA will represent the empty level (4mA) and 100% of 
the operational span (20mA), but you may wish to only represent a section 
of the operational span. For example, the application may have an 
operational span of 6 metres, but you may only wish to represent empty 
level to 5 metres. If so, change P834 (Low Value) to 0, and P835 (High 
Value) to 5.0.