PULSAR MEASUREMENT 
 
43 
 
Stability (StA) Menu 
Damping 
Damping is used to damp the display, to enable it to keep up with the 
process but ignore minor surface fluctuations. 
P870 Fill Damping 
This parameter determines the maximum rate at which the unit will respond 
to an increase in level. It should be set slightly higher than the maximum 
vessel fill rate. Default = 10.000 metres/minute (32.81 feet/minute) 
P871 Empty Damping 
This parameter determines the maximum rate at which the unit will respond 
to a decrease in level. It should be set slightly higher than the maximum 
vessel empty rate. Default = 10.000 metres/minute (32.81 feet/minute) 
System (SyS1) Menu 
The following three parameters do not affect how the unit performs, but 
details, contained in them, may be required, by Pulsar, when making technical 
enquiries. 
P921 Enable Code 
Enables the passcode (P922), which means the passcode must be entered 
to go into program mode. If disabled (set to 0), then no passcode is 
required, and pressing ESC and ENTER button simultaneously will allow entry 
into the program mode. 
P922 Passcode 
This is the passcode that must be used to enter program mode. The default 
is 1997, but this can be changed to another value. 
P926 Software Revision 
This parameter will display the current software revision.  
P928 Serial Number 
This parameter will display the serial number of the unit.