PULSAR MEASUREMENT
39
Display (DiSP) Menu
P800 Display Units
This parameter determines whether the reading displayed is in
Measurement Units (P104), or as a percentage of span.
Display in Measurement Units (P104)
Display is in Percentage of span
P801 Decimal Places
This parameter determines the number of decimal places on the reading
during run mode.
Minimum = 0 (No decimal places), Maximum 3 = (3 decimal Places)
Default = 2
P808 Fail-safe Mode
By default, if a fail-safe condition occurs, then the display, relays and the mA
output are held at their last known values until a valid reading is obtained.
If required, then you can change this so that the unit goes to high (100% of
span), or low (empty) as follows:
Remain at the last known value
Will fail to the high value (100% of span)
Will fail to the low value (empty)
P809 Fail-safe Time
In the event of a fail-safe condition occurring the fail-safe timer determines
the time before fail-safe mode is activated. Default = 2.00 mins
If the timer activates, the unit goes into fail-safe, as determined by P808,
(Display and P840 (mA Output). When this happens, you will see the
message “LOE!” on the display.
When a valid measurement is obtained then the display, relays and mA
output will be restored and the timer is reset.