Page 9
Fig. 3.
Echo profile after product has entered tank.
P021 Set Dist 1
Allows the user or service personnel to determine which echo is to be displayed.
On start up, if the unit displays an incorrect reading then simply enter the distance
from the transducer to the required level and, if an echo is present at this point,
the Gate will establish itself around the chosen echo, DATEM will update in front
of the Gate and reference out any other unwanted echoes.
It should be noted that DATEM will reset to default values whilst performing this
function, and reform itself once it has selected an echo.
P021 can also be accessed via the Operator Password (Default 1997).
Options: Enter distance from the face of transducer to the target in units of
measurement P104
Values: Min. 0.000
Max. 99.00
Default = 0.000