Same as 4 = Lo, but
different identifier
Relay goes “ON” if value
is inside the zone
between the two
setpoints.
Relay Setpoints, P213, 223,
233, 243, 253, 263 and
P214, 224, 234, 244, 254,
264 can be set in any order
as the unit ‘knows’ that you
are setting an inbounds
alarm.
Relay goes “ON” if value
is outside the zone
between the two
setpoints.
Relay Setpoints P213, 223,
233, 243, 253, 263 and
P214, 224, 234, 244, 254,
264 can be set in any order
as the unit ‘knows’ that you
are setting an out of
bounds alarm.
When P211, 221, 231, 241, 251 = 4 (L0ss of Echo) or 5 (Loss of Clock)
This parameter has no function and will not be displayed.
When P211, 221, 231, 241, 251, 261 = 6 Pump Efficiency
This parameter assigns the alarm to the appropriate pump relay as detailed
below.
Alarm is assigned to pump on Relay 1
Alarm is assigned to pump on Relay 2
Alarm is assigned to pump on Relay 3
Alarm is assigned to pump on Relay 4
Alarm is assigned to pump on Relay 5
Alarm is assigned to relays designated as pump
The fourth parameter and the fifth parameter for each relay set the Alarm
“ON” and “OFF” points. For a high alarm, the “ON” is set higher than “OFF”.
For low alarm, then “ON” is set lower than “OFF”. See the appropriate alarm
ID, table (P212, 222, 232, 242, 252, 262) for further information.