EasyManua.ls Logo

Pulsar Zenith 140 - Page 75

Pulsar Zenith 140
161 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PULSAR MEASUREMENT
75
OPTION
DESCRIPTION
SETPOINTS
5 = LoLo
Same as 4 = Lo, but
different identifier
6 = In bounds
Relay goes “ON” if value
is inside the zone
between the two
setpoints.
Relay Setpoints, P213, 223,
233, 243, 253, 263 and
P214, 224, 234, 244, 254,
264 can be set in any order
as the unit ‘knows’ that you
are setting an inbounds
alarm.
7 = Out of bounds
Relay goes “ON” if value
is outside the zone
between the two
setpoints.
Relay Setpoints P213, 223,
233, 243, 253, 263 and
P214, 224, 234, 244, 254,
264 can be set in any order
as the unit ‘knows’ that you
are setting an out of
bounds alarm.
When P211, 221, 231, 241, 251 = 4 (L0ss of Echo) or 5 (Loss of Clock)
This parameter has no function and will not be displayed.
When P211, 221, 231, 241, 251, 261 = 6 Pump Efficiency
This parameter assigns the alarm to the appropriate pump relay as detailed
below.
OPTION
DESCRIPTION
0 = Off (Default)
Relay will not operate
1 = Relay 1
Alarm is assigned to pump on Relay 1
2 = Relay 2
Alarm is assigned to pump on Relay 2
3 = Relay 3
Alarm is assigned to pump on Relay 3
4 = Relay 4
Alarm is assigned to pump on Relay 4
5 = Relay 5
Alarm is assigned to pump on Relay 5
7 = All
Alarm is assigned to relays designated as pump
The fourth parameter and the fifth parameter for each relay set the Alarm
ON” and “OFFpoints. For a high alarm, the “ONis set higher than OFF”.
For low alarm, then ON” is set lower than OFF”. See the appropriate alarm
ID, table (P212, 222, 232, 242, 252, 262) for further information.

Table of Contents