53
ENFORCER V11 PROGRAMMING GUIDE
TIMER FUNCTION RANGE
Settle Time between nal exit input closing, and system arming. 0 - 255 seconds
Double Knock
Length of lter period applied to inputs with ‘Double Knock’
attribute.
0 – 75 seconds
Pre-Alarm
Delays ‘Intruder’ output signals if entry time has started. Pre-
alarm time must be set for at least 30 seconds to comply with
PD6662
0 – 255 seconds
Comm Fault Delay
Duration of communication fault before ‘Comms Fault’ alarm
triggered. NOTE: In the case of devices connected via the ATE
pins, this time is additional to that already applied by the ATE.
Please note: Arming this to ‘250’ disables line fault
monitoring and will not notify at the keypad/readers
0 – 250 seconds
Set Fail
Time after which ‘Set Fail’ operation will be invoked if exit
procedure not completed.
0 – 255 seconds
Fire Siren Time Cut o time for re alarm. ‘99’ means endless. 1 – 99 minutes
Set Fail Warning Time for which a set fail warning will be present. 0 – 99 seconds
Occupancy
This timer (set in hours) denes the period of time that any
zones with the occupancy attribute enabled must be trigger in.
0 - hours
Occupancy Suspend Denes the areas which will suspend the timer if armed. [ABCD]
Input NAT Days
NAT stands for Non-Activity Timer. This is used in conjunction
with the input attribute ‘Non Activity Input’, and will monitor
the chosen input for the selected number of days. At expiration
of timer, and if the input has not opened within that time, then
this will be stored in the panel log. Non Activity fault and there
will be an output activated if programmed to it. Send SMS
message if “Special Log” is on.
0-14 days
Input NAT Hours
NAT stands for Non-Activity Timer. This is used in conjunction
with the input attribute ‘Non Activity Input’, and will monitor
the chosen input for the selected number of hours. At
expiration of timer, and if the input has not opened within that
time, then this will be stored in the panel log. Non Activity fault
and there will be an output activated if programmed to it. Send
SMS message if “Special Log” is on.
00-23 hours
Wireless Supervision Time
This option is only applicable if wireless devices are installed. It
is the time window before a wireless supervision fault will be
signalled. For example: if the time is set for 2 hours, then any
device that doesn’t communicate with the wireless expander
within that period will cause a supervision fault. This must be
programmed to 2 hours or less for compliance to EN50131.
0-99 hours
Wireless Jamming Time
This option is only applicable if wireless devices are installed.
It is the time window that if a wireless device had its signal
‘blocked’ a fault would display. For example, if the time is set to
30 seconds, then if a wireless device is ‘jammed’ longer than 30
seconds a fault will be displayed. This must be programmed to
30 seconds or less (but not zero) for compliance to EN50131.
0-100 seconds
Service Time
This is a timer that can be set in days, and will display a
message to the user warning that a service is due. An engineer
code will clear the message.
367 days