SERVICE STG
Parameter >
Maintenance >
Functions >
Operation mode >
Diagnostics >
PARAMETER
Driving cycle >
Time delay open >
Drive >
Entrance system >
MS 2-leaves >
Manual control >
MS 2-LEAVES
Function Ext. Sw 0
Overlap 5
Sequ. control open. 5
Sequ. control clos. 15
FUNCTION EXT. SW
0 Master+slave
1 Master only
SERVICE STG
Parameter >
Maintenance >
Functions >
Operation mode >
Diagnostics >
PARAMETER
Driving cycle >
Time delay open >
Drive >
Entrance system >
MS 2-leaves >
Manual control >
MS 2-LEAVES
Function Ext. Sw 0
Overlap 5
Sequ. control open. 5
Sequ. control clos. 15
OVERLAP
5
SERVICE STG
Parameter >
Maintenance >
Functions >
Operation mode >
Diagnostics >
PARAMETER
Driving cycle >
Time delay open >
Drive >
Entrance system >
MS 2-leaves >
Manual control >
MS 2-LEAVES
Function Ext. Sw 0
Overlap 5
Sequ. control open. 5
Sequ. control clos. 15
SEQU. CONTROL OPEN
5
SERVICE STG
Parameter >
Maintenance >
Functions >
Operation mode >
Diagnostics >
PARAMETER
Driving cycle >
Time delay open >
Drive >
Entrance system >
MS 2-leaves >
Manual control >
MS 2-LEAVES
Function Ext. Sw 0
Overlap 5
Sequ. control open. 5
Sequ. control clos. 15
SEQU. CONTROL CLOS.
15
Screens Available when synchronizing two operators
Both Simultaneous Pairs and Double Egress
This is automatically set by the controls
upon reading the Master / Slave jumper
block (J13) on the controls.
This sets the lead time and lag time
between operation of the master and
slave operators, useful with an over-
lapping astragal. When set above 0, the
Master begins opening before the slave
and will stop 10° before fully closed,
allowing the slave to close first. When
set to 0, operation is simultaneous.
This adjusts a delay time between
when the master operator begins
opening and when the slave begins.
Closing will not be affected. When set
to 0, operation is simultaneous.
This adjusts a delay time between
when the slave operator begins closing
and when the master begins closing.
Opening will not be affected. When set
to 0, operation is simultaneous.
When ordered as a dual synchronized pair or a double egress, the operators are factory wired and
parameters preset. If any changes are made, the following setup sequence is suggested -
Insure Jumper J14 is set to M1 on the master unit and set to S1 on the slave unit. Apply power to
both units, then press and hold the blue Control button on the master control for 8 flashes of the red
LED (reset to factory defaults). Next press and hold the Control button for 8 flashes on the slave control.
Return to the master unit and press & hold the Control button for 3 flashes of its red LED (initiate a
calibration run; allow the door to open then close). Finally, press & hold the button for 3 flashes on the
be configured for synchronous operation, and with the above parameters set to 0 providing simultaneous
operation. Note: If only one rocker switch is used, it is to be connected to the master control, and the slave
control parameter CONTROL PANEL / MECHANICAL PANEL should be set to 0, 3 Pos. (AUTO).
22
Learnin
Learnin
slave control.
The master unit should open again; the slave unit should follow. The units should now