EasyManua.ls Logo

Reliance flexpak plus - Page 42

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 6.C
TROUBLESHOOTING SUGGESTIONS FOR THE COMPLETE CONTROLLER (continued)
SYMPTOM
8. Drive motor does
not run with
M
contactor picked
up and SPEED
potentiometer
properly operat-
ing. (continued)
9. Drive motor does
not run with
M
contactor picked
up and SPEED
potentiometer
properly operat-
ing.
(Use this proce-
dure
only if
controller has
optional Test
Meter Adapter
Kit.)
1 0. Remote Operator
Control Station
functions not
operating.
PROBABLE CAUSE
Regulator Module sus-
pected because no out -
put reading at A 1, A2 .
Power Cube suspected
because no output
reading at A 1. A2.
No
gate firing pulses .
Malfunctioning
switches .
RECOMMENDED PROCEDURES
D Test the Regulator Module for fir ing pulses .
D Open the power disconnect swi tch.
D Locate on the Regulator Module a connector near the edge directly above the Maximum Speed
potentiometer . (Refer to Figure 6.4.) This connector has four sets of twi sted red and whi te w ires
going into it.
D Gently I ift the connector off the pins . Move it aside to a position w here it cannot cause shorts or
grounds .
D Connect the leads of the VOM to pins L 1 and G 1. (These pins are identified on the Module.) Refer
to Figur e 6.4 .
D Restore power to controller .
D Place the START / STOP switch in the START position.
D Turn the SPEED potentiometer to 10.
D The reading on the VOM should be \/
2
VAC for proper operation .
D If this reading cannot be obtained , replace the Regulator Module.
D In turn . repeat this same test with pins l2 / G2. 47 / G3. 47/ G4.
D Establish that the Power Cube is receiving pulse in puts at the conn ector on the Regul ator Module .
(Refer to "Regulator Module suspected," Symptom 8.)
D If the Power Cube is receiving pulses yet there is no reading across A 1 and A2 . dete rmin e that the
main contacts on the M contactor are closing .
D In order to check the contacts. replace the drive motor wi th a light bulb on the armat ure wiri ng at
1TB. (On 230 VAC controllers use two light bulbs in series .)
D If the light does not light. replace the Power Cube.
D Turn off power to the controller at the main disconnect .
D Connect a volt-ohmmeter lead to test pin 356 on the Test Meter Module .
D Connect the second lead to test pin 817 .
D Restore power to the controller .
DANGER
THE PROCEDURE DESCRIBED HERE IS PERFORMED WITH LIVE A-C VOLTAGE
APPLIED TO THE CONTROLLER . USE ONLY ONE HAND TO APPLY VOM LEADS /
PROBES. KEEP YOUR OTHER HAND BEHIND YOU AT ALL TIMES . DO NOT HOLD
ONTO THE CONTROLLER FOR SUPPORT . PERSONAL INJURY MAY RESULT IF
THESE PRECAUTIONS ARE NOT TAKEN.
D Place the START / STOP switch in the START position .
D On the + 10
voe scale of the volt-ohmmeter . an increase of approximatel y + 1 VOC should be
noted.
D Turn off
power to the controller .
D Reconnect the volt-ohmmeter to test pins 356 and 816.
D On the + 10
voe scale of the volt-ohmmeter . an increase of approximately +1 VDC should be
noted.
D If voltage readings increase, the Power Cube is receiving puls es to its SCRs.
D
Make a last check of wiring 10 the Power Cube.
D
If wiring is correct, replace the Power Cube.
D Check START / STOP switch, but
first remove a-c line power at main disconnec t.
D Connect ohmmeter to terminal 32 on the Remote Operator Adapter .
D Touch probe to terminal 38 on the Remote Operator Adapter .
D Place switch in the START (closed) position.
D
If the switch is properly functioning , a short will be seen on the meter .
·o Check the STOP function . Place the RUN/ JOG sw itch in the RUN position. Connect the ohmmete r
to terminals 32 and 35 . Place the switch in the STOP posit ion. whic h should open it if it is
functioning correctly . If there isa short. it will be seen on the meter .
If there is no short . the circu it is
opened. and the switch is functioning correct ly.
D Using similar techniques , test the RUN/ JOG sw itch in the RUN posit ion at termin als 32 and 35 .
When the switch is in the RUN position , a short should be read.
42
i
>

Table of Contents