EasyManua.ls Logo

Reliance flexpak plus - Page 41

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
'
Table 6.C
TROUBLESHOOTING SUGGESTIONS FOR THE COMPLETE CONTROLLER (continued)
SYMPTOM
5.
M contactor picks
up but remains
in only when
START pushbut-
ton is pressed
and held in .
6. Drive motor does
not run, but M
contactor and
CR pull up.
(Use this proce-
dure only if con·
troller does not
have optional Test
Meter Adapter
Kit.)
7. Drive motor does
not run. but
M
contacto r and
CR pull up.
(Use this proce -
dure
only if
controller
has
optional Test
Meter Adapter
Kit.)
8. Drive motor does
not run with
M
contactor picked
up and SPEED
potentiometer
properly operat ing.
(Use this proce-
dure only if con-
tro ller does
not
have optional Test
Meter Adapter
Kit.)
Continue this
symptom on next
page
PROBABLE CAUSE
RUN/ JOG switch is
in JOG postion .
CR relay not picking up.
No input signal from
SPEED potentiom eter
on Control Station .
No input signal from
SPEED pot.
No output from
Power Cube.
RECOMMENDED PROCEDURES
D Place the RUN/ JOG switch in the RUN position.
D
Connec~olt -ohmm;;;;; on the Re~ Operator Adapt;:i;lac-;;Tt°on wminal 35 . -- --
0 Connect th e second probe to connection 139 (orange wi re) connected to the FlexPak Plus M
contac tor.
0 The reading should be +24 VDC for normal operation. (Refer to Figure 6.5 to see the logic of this
test.)
D
Next, shift the probe from terminal 35 to terminal 38 on the same termina l board. However , leave
the second probe where it is.
D Press the ST ART switc h. The reading should be approximately 24 VDC for normal operation . (Refer
to Figure 6.5 to see the logic of this test .)
D Press the START / STOP switch to STOP. and then START. A 24 VOC (approximate) reading should
conti nue to appear . If it does not. the CR relay is not picking up. In this case. replace the Regulator
Module.
D If the controller does not have an optional AUTO/ MANUAL switch , inspect the Regulator
Module to determine that jumper J4 i1 in
piece . (The jumper is removed when the AUTO/
MANUAL swi tch is installed.)
D Check the SPEED potentiometer on the Control Station.
First. open the power disconnect
switch .
D Connect a volt-ohmmeter to the Regulator Module Remote Operator Adapter inputs . Connect one
lead to terminal 28. Connect the other to terminal 20. (Refer to Figure 3.4 for a Remote Station .)
D For proper operation. the reading should be 5K ohms .
D Disconnect the VOM lead from terminal 20. Connect it to terminal 426 .
D Turn the SPEED potentiometer from 10 to 0. The resistance should vary from 5K to O ohms. If it
does not, replace the potentiomete r.
D First check the main
power supplie s. This must be done with power applied to the FlexPak Plus
controller .
DANGER
THE PROCEDURE DESCRIBED HERE IS PERFORMED WITH LIVE A ·C VOLTAGE
APPLIED TO THE CONTROLLER. USE ONLY ONE HAND TO APPLY VOM LEADS /
PROBES . KEEP YOUR OTHER HAND BEHIND YOU AT ALL TIMES. DO NOT HOLD
ONTO THE CONTROLLER FOR SUPPORT. PERSONAL INJURY MAY RESULT IF
THESE PRECAUTIONS ARE NOT TAKEN.
D Connect one lead of volt-ohmmeter to test pin 357 on the Test Meter Adapter Module.
D Connect the second lead to test pin 356 on the Module .
D The reading should be within the range of 10.8 to 11.5 VDC for normal operation .
D Next. remove the lead from pin 356 . Place it on pin 456.
D The reading should be within the range of + 16 to + 28 VOC for normal operation.
D
Next, remove the lead from pin 456 . Place it on pin 471 .
D The reading should be within the rang e of -16 to - 28 VOC for normal operation.
D If th e proper reading s are obtained. the power supplie s may be assumed to be operating correctly.
D
If iacorrect readings are obtained, replace the Regulator Module .
D
Next. check the ref erence voltage input signal. (Thi s chang es in direct proportio n to an increase of
SPEED potentiometer voltage caused
by a turning of the dial.)
D Connect one lead of a volt-ohmm eter to pin 357 on the Test Meter Adapter Module .
D Connect the other lead to pin 826 . Readings vary from Oto + 8.2 VDC, depending on the set point of
the SPEED potentiometer dial.
D If no voltage is noted between pins 357 and 826 , check to see if jump er J4 on the Regulator Module
is properly placed/ removed for the specific controller . (It is to be in place, as factory -shipped, if
there is no AUTO/ MANUAL switch . It is to be removed if there is an A UTO/ MANUAL switch.)
D If the SPEED potentiomete r is functioning normally , and if the J4 jumper is placed/ removed, as
necessary, replace the Regulator Module .
D Examine armatur e wiring . First. open the power disconnect switc h.
D Check armature wiring for loose connections.
D Turn a-c power on again .
DANGER
THE PROCEDURE DESCRIBED HERE IS PERFORMED WITH LIVE A -C VOLTAGE
APPLI ED TO THE CONTROLLER. USE ONLY ONE HAND TO APPLY VOM LEADS /
PROBES . KEEP YOUR OTHER HAND BEHIND YOU AT ALL TIMES. DO NOT HOLD
ONTO THE
CONTROLLER FOR SUPPORT. PERSONAL INJURY MAY RESULT IF
THESE PRECAUTIONS ARE NOT TAKEN.
D Connect a volt-ohmmeter to terminals A 1 and A2 on 1 TS. (Refer to Figure 3.4.)
0 Place the START/ STOP switch in the START position .
D Increase the speed reference by turning the SPEED dial in the direction of 10.
O The reading across A 1 andA2shouldbe Oto90VOCfor 115VAC contr ollers. It should be Oto 180
for 230 VAC controller s.
D
If no reading is obtained across A 1 and A2, it may be necessary to replace the Power Cube and/ or
the Regulator Module. In order to determine which , read on.
41

Table of Contents