If the “n” value on the gauge is set to 0.60 and the enclosure n is different, an error, as shown in Table 13
will result if the [@ Pressure] function is used at the Achieved Pressure to estimate result at 50 Pa.
Table 9: Errors in Estimated Flow at 50 Pa if gauge "n" = 0.60 differs from actual n
Actual Flow Exponent (n) of Enclosure
Achieved
Pressure (Pa)
Achieved pressure is the actual maximum pressure achieved in the enclosure during the test.
=
(
)
In the tables, the Pressure of Interest is 50Pa, and Assumed n is 0.65 or 0.60
The actual flow exponent n for an enclosure can be calculated by measuring building leakage at multiple
pressure differences, from 10 to 50 Pa, and determining the slope of the line: