Address Parameter Description
40037
Sys Power
System Power (Read Only) is the Nominal system power based on
the values of Nominal system volts and Nominal system current.
40041
Word Order Word Order controls the order in which the receives instrument
or sends oating - point numbers:- normal or reversed register
order.In normal mode, the two registers that make up a oating
point numbers are sent most signicant bytes rst.
In reversed register mode , the two registers that make up
a oating point numbers are sent least signicant bytes rst.
To set the mode, write the value ‘2141.0’ into this register-
the instrument will detect the order used to send this value and
set that order for all ModBus transaction involving oating point
numbers.
This address allows the user to set CT Primary value.
The maximum settable value is 9999 & also depends on the per
phase 666.6MVA Restriction of power combined with PT primary
40035
CT Pimary
40039
40033
PT Primary This address allows the user to set PT Primary value.
The maximum settable value is 692.8kV L-L
depends on the per phase 666.6MVA Restriction of power
combined with CT primary
This address is used to set the rollover count for energy. If
Energy on Rs485 is in Wh rollover count can be from 7 to 14.
If it is in KWh then rollover count can be from 7 to 12 & for MWh
rollover count can be from 7 to 9.
Energy digit
Reset Count
55

Table of Contents

Other manuals for Rish Master 3430

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rish Master 3430 and is the answer not in the manual?

Rish Master 3430 Specifications

General IconGeneral
BrandRish
ModelMaster 3430
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals