Address Parameter Description
40079
30mA Noise
current
Elimination
This address is used to activate or de-activate the 30 mA noise
current elimination write
0-Deactivate
30 (Decimal)-Activate
Writing any other value will return an error.
40081
Energy
Update
Rate
Energy Update Rate is the time after which energy registers
are updated. This time is user settable from 1 - 60 minutes.
40083
This Address is Read Only. This Address shows the Model
Number of the meter
Model
Number
to
40117
Energy
Start
Count
40107
The user can set respective energy starting count in these
registers (before the user can write values to these locations
user needs to check register 40005 i.e Energy on RS485 and
register 40036 i.e Energy digit reset count). Valid range is
0-9999999. For E.g if Energy on RS485 is in K and Energy
digit reset count is 7 the start count should be in k and
value should be less than 7 digits.
40077
Auto
Scroll
This address is used to activate or de-activate the Auto scroll
setting.
0-Deactivate
1 (Decimal)-Activate
Writing any other value will return an error.
57