GD-70D - 56 -
You can select the transmission status with the setting point of nciMaxSendHBb(12)
nciMaxSendHB (12) = Asec --> (6) transmit every Asec.
nciMaxSendHB (12) = 0sec --> (6) dont transmit every Asec.
It outputs to nvoComand (14) for input data of nviComand (13).
nviComand (13) = "A1, R," --> nvoComand (14) = "A1, R, ××××"
××× express 1st alarm point read value in hexadecimal.
nviComand (13) = "A2, R," --> nvoComand (14) = "A2, R, ××××"
×××× express 2nd alarm point read value in hexadecimal.
nviComand (13) = "AD, R," --> nvoComand (14) = "AD, R,××××"
×××× express Alarm delay time (mesc 10 units) read value in hexadecimal.