GD-70D - 82 -
First Alarm Contact
Setting
Select either nd(De-
Energized)/nE(Energized),
and then press the SET key
to confirm the selection.
(Press the MODE key to
skip this menu.)
Factory setting is nd.
nd
AL1 RLY
MAINTENANCE
/
nE
AL1 RLY
MAINTENANCE
Second Alarm Contact
Setting
Select either nd (De-
Energized)/nE (Energized),
and then press the SET key
to confirm the selection.
(Press the MODE key to
skip this menu.)
Factory setting is nd.
nd
AL2 RLY
MAINTENANCE
/
nE
AL2 RLY
MAINTENANCE
Fault Alarm Contact
Setting
Select either nd (De-
Energized)/nE (Energized),
and then press the SET key
to confirm the selection.
(Press the MODE key to
skip this menu.)
Factory setting is nd.
nd
FLT RLY
MAINTENANCE
/
nE
FLT RLY
MAINTENANCE
Return to
SET 6. RLY
PTRN
NOTE
When De-energized (nd) is selected, the relay is energized and activated during an alarm condition (de-
energized during normal operation).
When the alarm contacts are configured as normally open, the contacts are open during normal
operation and closed during an alarm condition.
When the alarm contacts are configured as normally closed, the contacts are closed during normal
operation and open during an alarm condition.
When Energized (nE) is selected, the relay is energized during normal operation (de-energized during an
alarm condition).
When the alarm contacts are configured as normally open, the contacts are closed during normal
operation and open during an alarm condition. They close if the power is turned OFF.
When the alarm contacts are configured as normally closed, the contacts are open during normal
operation and closed during an alarm condition.