Commissioning and Maintenance
24 © robatherm
Pos: 42.18 /Inbetri ebnahme und Wartung/Ven tilator/Ventilator _Wartung @ 0\mod_12579 58205121_2008.doc @ 2136 @
Fan – Periodic Maintenance
Check fan for hygiene, contamination, damage, corrosion and fastening
Check impeller for imbalance and vibrations; balance if necessary
Check bearings for noise, vibration and heat
Check flexible connection for leaks
Check functioning of vibration dampers
Check function of protective devices
Check function of inlet vane control
Check functioning of dehydration equipment
Check gap width of open impellers (see page 21); correct if necessary
Pollution and dirt on flex connector shall be removed with a vacuum cleaner, and, in a
second step, wiped with a with damp cloth
Fan – Maintenance when necessary
Replace bearings (no later than the end of the theoretical service life)
Grease bearing. Follow manufacturer’s instructions!
Clean fan, rectify any damage and corrosion, retighten fastenings
Electric Motor – Periodic Maintenance
Check electric motor for contamination, damage, corrosion, fastening, smooth running,
heating and direction of rotation
Check bearings for noise, vibration and heat
Clean electric motor and rectify any damage and corrosion
Measure tension, current input and phase symmetry
Check firm seating of terminals in terminal block; retighten if necessary
Check protective conductor; retighten or replace if necessary
Check cable rails. Clean it if necessary with vacuum cleaner and, if necessary with damp
cloth
Electric Motor – Maintenance when necessary
Replace bearings (no later than the end of the theoretical service life)
Grease bearing. Follow manufacturer’s instructions!
Belt Drive – Periodic Maintenance
Check belt drive for contamination, damage, wear, tension, alignment of motor and fan
pulley (tolerance < 0.4°; d.h. < 7 mm/m), check function and fastening (see torque
settings)
Check protective device for damage, fastening and functioning
Belt Drive – Maintenance when necessary
Replace belt set
Adjust alignment of motor and fan pulley
Adjust belt tension (see page 26)
Clean belt drive