Installation RMC / RZ / RM / RL
8 © robatherm
Pos: 19 /Überschrif ten/__Montage und Aufste llung @ 0\mod_12573413 66915_2008.doc @ 2039 @ 2
Assembly and Installation
Pos: 20.1 /Montage/_G eräteaufstellung @ 0\ mod_1257504279322_200 8.doc @ 2075 @ 3
Unit Installation
Pos: 20.2 /Sicher heitshinweise/Montage/ !Montage_Montage& Aufstellung_Geräte aufstellung_Ach tung @ 0\mod_12575043294 95_2008.doc @ 2076 @
Attention
robatherm units must not take on any functions of the building itself.
If a unit is misused, for example by substituting base of unit for building roof or by allocating
static functions to the unit, all warranty obligations on the part of robatherm will lapse.
Observe the notes in VDI 3803.
Pos: 20.3 /Montage/Mo ntage&Aufstellung_Fu ndament @ 0\mod_12575 04447012_2008.doc @ 2077 @ 44
Foundation
Install units on a firm and flat foundation. Any unevenness, leading to non-parallel frames of
connecting parts, must be flattened out with suitable supports (metal strips or equivalent).
Maximum tolerance to the horizontal is s = 0.5 % (max angle of inclination: 0.3°).
The foundation must conform to the building requirements in terms of statics, acoustics and
proper water drainage (drip pan, air humidifier, etc.). Structural beams must be one single
piece over their entire length. The maximum beam distortion is 1/1000 of the beam length.
The distance between horizontal beams may not exceed 24 modules (2.5 m) (see robatherm
planning recommendations).
The natural frequency of the supporting structure, especially steel supports, must be
separated adequately from the exciter frequency of rotating components of e.g. fans, motors,
pumps, compressors etc,
Standing Safety
Units installed outside must be secured to the foundations in accordance with the expected
wind speed at the place of installation. This applies for all units with integrated motor
extraction device.
Pos: 20.4 /Montage/Mo ntage&Aufstellun g_Hebezeuge @ 0\mod_125750 5057509_2008.doc @ 2079 @ 4
Lifting Gear
Only use suitable and permitted lifting gear for assembly. Only apply lifting gear at the top
edge of the base frame to avoid any deformations.
Pos: 20.5 /Einleitu ng/Technikzentra le @ 0\mod_1256574615063 _2008.doc @ 2016 @ 4
Mechanical Equipment Room
The requirements of mechanical equipment rooms must be observed in accordance with the
VDI 2050 for operations and maintenance. This also includes sufficient maintenance space,
ventilation as well as compliance with the temperature and humidity requirements.
In front of heating and cooling coils, it is recommended to allow an obstacle-free area, at
least as wide as the AHU’s depth for maintaining those coils.