Commissioning and Maintenance
© robatherm 21
Pos: 42.1 /Überschri ften/__Ventilator und Motor @ 0\mod_1257341370 681_2008.doc @ 2042 @ 2
Fan and Motor
Pos: 42.2 /Inbetri ebnahme und Wartung/_Inbe triebnahme @ 0\mod_12579 29574289_2008.doc @ 2116 @ 3
Commissioning
Pos: 42.3 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 42.4 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Ventilator_IBN _Vorsicht @ 0\mod_1257956 996526_2008.doc @ 2127 @
Caution
Serious bodily injuries or even loss of life and material damage can be caused by the
breakage of the impeller. Do not exceed maximum fan speed as per nameplate and
technical data sheet. Do not operate fan if there are abnormal vibrations.
There is a danger of fire through grinding impeller, belt, hot running bearings.
Danger to health through noise (up to approx. 110 dB).
Pos: 42.5 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_ATEX-Bauteile erden @ 0\ mod_1257956926546_2 008.doc @ 2126 @
Only use approved parts with ATEX units. All electrical parts must be earthed.
Pos: 42.6 /Inbetri ebnahme und Wartung/Venti lator/Ventilator _IBN_Transportsi cherung @ 0\mod_12579572 30386_2008.doc @ 2128 @ 4
Transportation Safety Device
Remove transportation safety devices (wooden wedges or locking plates) from base frame of
fan. Avoid pulling vibration isolators.
Pos: 42.7 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Ventilator_IBN _Achtung @ 0\mod_1257957 311881_2008.doc @ 2129 @
Attention
Before commissioning check unit and duct system for foreign bodies (tools, small parts,
building dust) and clean if necessary.
Rotate impeller by hand to check for free running.
Pos: 42.8 /Inbetri ebnahme und Wartung/Venti lator/Ventilator _IBN_Freilaufend e Räder @ 0\mod_12579573816 74_2008.doc @ 2130 @ 4
Plug Fans
During transportation the circumferential gap between the impeller and inlet nozzle may
change. Measure the gap width before commissioning. The gap must be the same width
round the whole circumference; if necessary correct the gap at the vibration damper using
lock nut and adjusting nut (1).
The overlap (R) must be about 1% of the impeller diameter.
There is no need to perform this check for an open impeller with flexible connection.