Commissioning and Maintenance
© robatherm 47
Pos: 62.1 /Überschri ften/__Entfeucht ungsrotor @ 0\mod_1257341 713529_2008.doc @ 2050 @ 2
Desiccant Rotor
Pos: 62.2 /Inbetri ebnahme und Wartung/_Inbe triebnahme @ 0\mod_12579 29574289_2008.doc @ 2116 @ 3
Commissioning
Pos: 62.3 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 62.4 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Rotor-WRG_Vorsi cht @ 0\mod_125839016885 1_2008.doc @ 2181 @
Caution
When current feed is not disconnected at all poles, there is a risk of crushing and scraping
to the limbs through sudden running of the rotor caused by an automatic cleaning run or
automatic re-start after power failure.
Pos: 62.5 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Entfeuchtungsro tor_Achtung @ 0\mod_12 58443758050_2008.doc @ 2193 @
Attention
If commissioning is not undertaken correctly, overheating, frost damage, erosions of the
rotor body or odor problems may occur depending on the type of rotor. It is compulsory to
observe the rotor manufacturer’s information (request if necessary)!
Do not operate LICI-rotors with e.g. supersaturated air or clean wet.
The commissioning must be carried out in accordance with the rotor manufacturer’s
instructions and the commissioning described by robatherm (see page 42).
Pos: 62.6 /Inbetri ebnahme und Wartung/Entfeuc htungsrotor/En tfeuchtungsrotor _Rotordrehzahl @ 0\mod_1 258443875981_2008. doc @ 2194 @ 44
Rotor Speed
The desiccant rotor requires a much lower speed during dehumidification than during HRS
operation. The defined rotor speeds have to be checked, e.g. during dehumidification 10 1/h
for 2 V input signal (or the priority contact is closed) and in HRS operation 10 1/min for 10 V
input signal.
Pressure Drop
In order to avoid contamination of the supply air with the humid regeneration air, the
pressure potential of the fans should be selected in such a way that the system related
leakage from the supply air side flows into the regeneration air side.
Pos: 62.7 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_ATEX_Zonenversc hleppung @ 0\mod_12583904 80461_2008.doc @ 2183 @
Zone crossing must be avoided with ATEX units in all circumstances.