Commissioning and Maintenance
40 © robatherm
Pos: 54.1 /Überschri ften/__Kälteanlage und W ärmepumpe @ 0\mod_125 7341719170_2008.doc @ 2055 @ 2
Refrigeration Installations and Heat Pump
Pos: 54.2 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 54.3 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Kälteanlage_Vor sicht @ 0\mod_12583896 91566_2008.doc @ 2178 @
Caution
Avoid any physical contact with the refrigerant as this may cause frostbite to the skin and
limbs or retinal damage. Use personal protection equipment against effects of refrigerants
VBG 20 (goggles, gloves, etc.)!
Refrigerant (odourless and tasteless) ejects atmospheric oxygen and can cause
suffocation. TLV values (for R407C: 1,000 ppm in 8h) and practical value limit DIN 8960
(for R407C: 0.31 kg/m³ area) must be observed. If refrigerant does escape only enter the
machine room with heavy duty respiratory protective gear. Observe the safety data sheet.
Refrigerants and compressor oil develop toxic, noxious substances in tandem with naked
flame. Do not inhale! Do not smoke in the machine room!
There may be an allergic reaction if compressor oil is touched or swallowed. Avoid physical
contact! Observe safety data sheet.
Pos: 54.4 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_ATEX-Bauteile erden @ 0\ mod_1257956926546_2 008.doc @ 2126 @
Only use approved parts with ATEX units. All electrical parts must be earthed.
Pos: 54.5 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Kälteanlage_Ach tung1 @ 0\mod_12583895976 65_2008.doc @ 2177 @
Attention
Completion and commissioning of refrigeration installations may only be carried out by the
manufacturer or another expert assigned by the manufacturer; maintenance and servicing
work only by qualified personnel.
For all work the requirements of the service booklet (request if required), and the valid
standards and guidelines (e.g. DIN EN 378, BGR 500 and EC-F Gas Directive) must be
adhered to.
Pos: 54.6 /Inbetri ebnahme und Wartung/Kältea nlage/Kälteanla ge_Wiederkehrende Prüf ungen @ 0\mod_1258389415 926_2008.doc @ 2176 @ 44444
Recurring Inspections
According to §15 of the German Industrial Safety Regulation (BetrSichV), the units and unit
parts underlie recurring inspections by an authorized person respectively accredited
inspection agency. Further applicable statutory provisions of the respective location are to be
observed.
Commissioning Requirements
All construction requirements such as access, completed unit and duct installation and
uninterrupted availability of all supply facilities must be met. In addition there must be a
possibility of operating the system in the required working phases.
Basis for Warranty
The basis for the warranty is built on a maintenance contract with a qualified company
specialised in refrigeration engineering together with records of performance of maintenance
work.