Commissioning and Maintenance
64 © robatherm
Pos: 70.1 /Überschri ften/__Hochdruck- Sprühbefeuchter @ 0\ mod_1257341717967_2008. doc @ 2054 @ 2
High Pressure Spray Humidifier
Pos: 70.2 /Inbetri ebnahme und Wartung/_Inbe triebnahme @ 0\mod_12579 29574289_2008.doc @ 2116 @ 3
Commissioning
Pos: 70.3 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 70.4 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Hochdruck-Sprühbef euchter_IBN_Vor sicht @ 0\mod_1258477857 280_2008.doc @ 2234 @
Caution
For further information the individual commissioning instructions must be observed!
Pos: 70.5 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_ATEX-Bauteile erden @ 0\ mod_1257956926546_2 008.doc @ 2126 @
Only use approved parts with ATEX units. All electrical parts must be earthed.
Pos: 70.6 /Inbetri ebnahme und Wartung/Hochdr uck-Sprühbefeuc hter/Hochdruck- Sprühbefeuchter_IB N @ 0\mod_1258477938884_2008. doc @ 2235 @ 4444
Fresh Water
Completely desalinated water (permeate from reverse osmosis) with max. 20 µS/cm and
total water hardness max. 1 °dH.
Water quality following VDI 6022, VDI 3803
, DIN EN 13053
and Drinking Water Ordinance
Water supply pressure: 2 to 8 bar
Drinking water connections shall be equipped with pipe isolators according to EN 1717.
High Pressure Connection
Check that high pressure hose is routed so that it is not subject to stretching or chafing;
correct if necessary.
Check threaded connections to humidifier and pump station for leaks; tighten if
necessary. Use a second wrench for counter tightening.
Internal bolts must not be retightened.
Pump Station
Check oil level through sight glass or with a dipstick; if necessary top up with required
type of oil (see information on pump station).
Check tension of drive belt; retension with pulley if necessary.
Check discharging screw for leaks; retighten if necessary. For this use a second wrench
to counter turn.
Set system in motion manually and check basic functions.
Check pump direction of rotation, if it is incorrect swap electrical connections.
Check protective devices as instructed.
Control Unit
Commission control unit as instructed.