Commissioning and Maintenance
© robatherm 35
Pos: 50.1 /Überschri ften/__Elektro-Luf terwärmer @ 0\mod_1257 341375744_2008.doc @ 2046 @ 2
Electric Heater
Pos: 50.2 /Inbetri ebnahme und Wartung/_Inbe triebnahme @ 0\mod_12579 29574289_2008.doc @ 2116 @ 3
Commissioning
Pos: 50.3 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 50.4 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_heiße F lächen @ 0\mod_1258373421 988_2008.doc @ 2158 @
Caution
To avoid burns, do not touch hot surfaces.
Pos: 50.5 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_ATEX-Bauteile erden @ 0\ mod_1257956926546_2 008.doc @ 2126 @
Only use approved parts with ATEX units. All electrical parts must be earthed.
Pos: 50.6 /Inbetri ebnahme und Wartung/Elektr o-Lufterwärmer/ Elektro-Lufterwär mer_Sicherheits- Temperaturbegrenzer @ 0\mod_1258387695243_20 08.doc @ 2168 @ 44
Safety Temperature Limiter
Each electric heater must be equipped with a fully tested safety temperature limiter with
manual reset. Test function with hot air drier.
Recommendation
Triple thermostat mounted directly downstream from electric heater:
“Fan” setting: 40 °C.
“Safety temperature limiter” setting: 70 °C.
Pos: 50.7 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Elektro-Lufter wärmer_IBN_Achtung @ 0\ mod_1258387913996_200 8.doc @ 2170 @
Attention
Electric heaters may only be operated if flow control is present.
Overheating damage may occur to the electric heater, housing and other fitted parts if the
system is run with insufficient cooling (e.g. system switched off at the main switch when the
electric air heater is still on) or in the event of an emergency system shut down triggered by
safety devices.
Pos: 50.8 /Inbetri ebnahme und Wartung/Elektr o-Lufterwärmer/ Elektro-Lufterwär mer_Strömungs-Über wachung @ 0\mod_125838780 9768_2008.doc @ 2169 @ 44
Flow Control
The airflow is monitored by measurement of the pressure difference at the fan unit, using an
air pressure gauge Functioning must be checked during commissioning.
Current Consumption
The current consumption is to be checked at all phases by measuring all phases.
For rated data see nameplate.
If the rated values are exceeded, the robatherm Technical Service must be informed.