Commissioning and Maintenance
© robatherm 37
Pos: 52.1 /Überschri ften/__Luftkühler @ 0\mod_1257341710373_200 8.doc @ 2047 @ 2
Cooling Coil (CW – DX Coil)
Pos: 52.2 /Inbetri ebnahme und Wartung/_Inbe triebnahme @ 0\mod_12579 29574289_2008.doc @ 2116 @ 3
Commissioning
Pos: 52.3 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 52.4 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_Kontak t mit Sole @ 0\mod_12583731846 97_2008.doc @ 2156 @
Caution
Avoid any contact with brine while charging or venting. Danger of poisoning and acid burns!
Observe manufacturer’s instructions.
Pos: 52.5 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_heiße/ kalten Flächen @ 0\mod_12 58374632300_2008. doc @ 2162 @
Caution
To avoid burns, do not touch hot/cold surfaces.
Pos: 52.6 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Luftkühler_I BN_Achtung @ 0\mod_12583885 09696_2008.doc @ 2172 @
Attention
Do not exceed permissible pressure range.
To avoid freezing of the cooling coil:
Add anti-freeze agent or mount the cooling coil downstream from the pre-heater.
Pos: 52.7 /Inbetri ebnahme und Wartung/Luftk ühler/Luftkühler _Prüfung @ 0\mod_1258388 563834_2008.doc @ 2173 @ 4444
Inspection
Check inlet outlet connections for function (counter flow principle).
In the case of direct expansion coils, the nitrogen protection gas must escape with a hissing
noise following opening of the heat exchanger connections. Otherwise there is a leakage;
please inform our technical service.
Charging
The system must be rinsed (removal of contaminations) according to VDI 2035 and should
be filled with the heat exchanger fluid named in the design data sheet to the correct
concentration. Water quality to VDI 2035. Too high a concentration of glycol leads to
reduced performance, too low a concentration of glycol can lead to frost damage.
Venting
When charging the system according to VDI 2035 the air cooler and the system should be
vented carefully at the highest point of the system. For this purpose open the venting screw
at the top connection or open separate venting screw.
If incorrect venting takes place, cooling coils develop air locks which lead to a reduction in
capacity. Recommendation: Venting recovery system (stop-cock with hose nozzle).
After Commissioning
After commissioning check the screw fittings of the flange for leakage and retighten if
necessary (see page 12).