Commissioning and Maintenance
38 © robatherm
Maintenance
Pos: 52.9 /Inbetri ebnahme und Wartung/W artungsintervall_3Mona te/ATEX monatlic h @ 0\mod_1257930528679_20 08.doc @ 2122 @ 4
Maintenance Interval
Every three months. ATEX units every month.
Pos: 52.10 /Sicher heitshinweise/!Vor sicht_Sicherheits hinweise beachten_ Querverweis @ 0\mod_12577 77093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 52.11 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_Kontakt mit Sole @ 0\mod_1258373184 697_2008.doc @ 2156 @
Caution
Avoid any contact with brine while charging or venting. Danger of poisoning and acid burns!
Observe manufacturer’s instructions.
Pos: 52.12 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_heiße/k alten Flächen @ 0\mod_12583 74632300_2008.doc @ 2162 @
Caution
To avoid burns, do not touch hot/cold surfaces.
Pos: 52.13 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_Temper ieren auf Umgebungstemper atur @ 0\mod_1258373503 611_2008.doc @ 2159 @
Caution
Before starting work allow components to cool/warm up to the ambient temperature.
Pos: 52.14 /Inbetri ebnahme und Wartung/Luft kühler/Luftküh ler_Wartung @ 0\mod_1258388 701310_2008.doc @ 2174 @
Cooling Coil – Periodic Maintenance
Check cooling coil for hygiene, contamination on air side, damage, leaks and corrosion
Vent cooling coil
Check drip pan for contamination, clean if necessary
Check water outlet and siphon function, clean if necessary
Check water level in siphon refill if necessary
Check inlet / outlet for function
Check frost protection for function (determine anti-freeze concentration or thermostat by
means of cooling spray)
Check direct expansion for icing
Cooling Coil – Maintenance when necessary
Clean the cooling coil on the air side (see below), rectify damage, leakage and corrosion
Drop Eliminator – Periodic Maintenance
Check drop eliminator for hygiene, contamination, encrustation, damage, drip erosion and
corrosion
Drop Eliminator – Maintenance when necessary
Clean and service eliminator: Pull out cassette, disassemble and clean profiles
separately; rectify damage and corrosion
Pos: 52.15 /Inbetri ebnahme und Wartung/Luft kühler/Luftküh ler_Wartung_Reinigu ng @ 0\mod_1258389000184 _2008.doc @ 2175 @ 44
Cleaning
Clean heat exchangers already assembled or if not accessible pull them out for cleaning.
Contamination which has been removed must not enter adjoining unit parts. Remove dirt and
contaminated water carefully.
Observe the following points:
Avoid bending plate fins
Blow out with compressed air in the opposite direction
Do not use a high pressure cleaner or a high pressure steam cleaner
Clean with water and low pressure
Cleaning Agents
Use cleaning agents with a pH-value between 7 and 9 if required.