Commissioning and Maintenance
© robatherm 45
Pos: 58.1 /Überschri ften/__Platten-W RG @ 0\mod_1257341722904_200 8.doc @ 2058 @ 2
Plate Heat Exchangers
Pos: 58.2 /Inbetri ebnahme und Wartung/_Inbe triebnahme @ 0\mod_12579 29574289_2008.doc @ 2116 @ 3
Commissioning
Pos: 58.3 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 58.4 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Platten-WRG_IB N_Achtung @ 0\mod_12583911 61268_2008.doc @ 2186 @
Attention
In order to avoid damage to the heat exchanger, do not exceed the maximum permissible
pressure drop SUPPLY/EXTRACT (depending on type approx. 1,000 Pa). Observe notes
for closing dampers (see page 19)
Pos: 58.5 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_ATEX_Zonenversc hleppung @ 0\mod_12583904 80461_2008.doc @ 2183 @
Zone crossing must be avoided with ATEX units in all circumstances.
Pos: 58.6 /Inbetri ebnahme und Wartung/Plat ten-WRG/Platten-W RG_Prüfung @ 0\mod_1258391 245747_2008.doc @ 2187 @ 4
Inspection
Check (and clean if necessary) plate heat exchanger for foreign particles and contamination
(see below).
Pos: 58.7 /Inbetri ebnahme und Wartung/_W artung @ 0\mod_125792958525 7_2008.doc @ 2117 @ 3
Maintenance
Pos: 58.8 /Inbetri ebnahme und Wartung/W artungsintervall_3Mona te/ATEX monatlic h @ 0\mod_1257930528679_20 08.doc @ 2122 @ 4
Maintenance Interval
Every three months. ATEX units every month.
Pos: 58.9 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 58.10 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Achtung_Reinigung W ärmeübertrager @ 0\mod_125 8373727824_2008.d oc @ 2160 @
Attention
In order to avoid damage when cleaning, air or water jet should only be directed onto the
surfaces of the heat exchanger at a right angle.
Pos: 58.11 /Inbetri ebnahme und Wartung/Plat ten-WRG/Platten-W RG_Wartung @ 0\mod_1258391 302056_2008.doc @ 2188 @
Plate Heat Exchanger – Periodic Maintenance
Check plate heat exchanger for hygiene, foreign bodies, contamination, damage and
corrosion
Check water outlet and siphon function, clean if necessary
Check water level of siphon, top up if necessary
Plate Heat Exchanger – Maintenance when necessary
Rectify foreign bodies, contamination, damage and corrosion
Clean with compressed air or high pressure cleaner (only water without additives);
remove dirty water carefully