Commissioning and Maintenance
44 © robatherm
Maintenance
Pos: 56.10 /Inbetri ebnahme und Wartung/W artungsintervall_3 Monate/ATEX monatlic h @ 0\mod_1257930528679_2 008.doc @ 2122 @ 4
Maintenance Interval
Every three months. ATEX units every month.
Pos: 56.11 /Sicher heitshinweise/!Vor sicht_Sicherheits hinweise beachten_ Querverweis @ 0\mod_12577 77093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 56.12 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Rotor-WRG_Vorsic ht @ 0\mod_1258390168851_2 008.doc @ 2181 @
Caution
When current feed is not disconnected at all poles, there is a risk of crushing and scraping
to the limbs through sudden running of the rotor caused by an automatic cleaning run or
automatic re-start after power failure.
Pos: 56.13 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Achtung_Reinigung W ärmeübertrager @ 0\mod_125 8373727824_2008.d oc @ 2160 @
Attention
In order to avoid damage when cleaning, air or water jet should only be directed onto the
surfaces of the heat exchanger at a right angle.
Pos: 56.14 /Inbetri ebnahme und Wartung/Rotor -WRG/Rotor-W RG_Wartung @ 0\mod_125839057701 4_2008.doc @ 2184 @
Rotary Heat Exchanger – Periodic Maintenance
Check rotary heat exchanger for hygiene, foreign bodies, contamination, damage and
corrosion
Check sealing strips for contamination, foreign bodies and contact pressure (see above)
Check drive belt for wear and tension, shorten (see above) or change if necessary
Check rotor for imbalance and lateral trueness
Check bearing for incorrect heating, vibrations or running noises and change if necessary
(no later than the end of the theoretical service life)
Check water outlet and siphon function clean if necessary
Check water level of siphon, top up if necessary
Check functioning of rotor control, align sensor if necessary
Rotary Heat Exchanger – Maintenance when necessary
Rectify foreign bodies, contamination, damage and corrosion
Clean rotor body with compressed air or high pressure cleaner (only water without
additives); remove dirty water carefully
Clean sealing strips, change if there is abrasion
Adjust contact pressure of sealing strips (see above)
Balance or align rotor
Pos: 56.15 /Inbetri ebnahme und Wartung/Rotor -WRG/Rotor-WRG_War tung_Außerbetriebs etzung @ 0\mod_12583908 78692_2008.doc @ 2185 @ 4
Shut Down
If rotor is out of action for a longer period (e.g. summer), turn it on intermittently to maintain
self-cleaning function.
Pos: 57 /Layout/Seite numbruch @ 0\mod_12566286 15637_0.doc @ 2284 @