Commissioning and Maintenance
© robatherm 31
Pos: 48.1 /Überschri ften/__Lufter wärmer @ 0\mod_1257341374509 _2008.doc @ 2045 @ 2
Heating Coil (Hot Water, Steam)
Pos: 48.2 /Inbetri ebnahme und Wartung/_Inbe triebnahme @ 0\mod_12579 29574289_2008.doc @ 2116 @ 3
Commissioning
Pos: 48.3 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 48.4 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_heißes Medium @ 0\mod_125837330131 9_2008.doc @ 2157 @
Caution
Do not use any hot medium while filling, bleeding air or removing as there is a danger of
scalding.
Pos: 48.5 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_heiße F lächen @ 0\mod_1258373421 988_2008.doc @ 2158 @
Caution
To avoid burns, do not touch hot surfaces.
Pos: 48.6 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Vorsicht_Kontak t mit Sole @ 0\mod_12583731846 97_2008.doc @ 2156 @
Caution
Avoid any contact with brine while charging or venting. Danger of poisoning and acid burns!
Observe manufacturer’s instructions.
Pos: 48.7 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Lufterwärmer_I BN_Achtung @ 0\mod_12583747 53313_2008.doc @ 2163 @
Attention
Do not exceed permissible pressure range (see design data sheet).
To avoid freezing of the heating coil:
Add anti-freeze agent or install frost protection control on air, water or condensate side
depending on unit design.
To avoid any overheating damage to the unit, run steam coil only when fan is running
Provide air flow control or temperature limiter.
Pos: 48.8 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Lufterwärmer_I BN_ATEX @ 0\mod_1258374903 528_2008.doc @ 2164 @
Ensure sufficient distance between max. surface temperature of the heat exchanger due to
temperature of the medium and minimum ignition temperature of any flammable mixture
which may be present in accordance with EN 1127.
Pos: 48.9 /Inbetri ebnahme und Wartung/Lufter wärmer/Lufter wärmer_Prüfung @ 0\mod_125 8374972714_2008.d oc @ 2165 @ 4444
Inspection
Check inlet outlet connections for function (counter flow principle).
Charging
The system must be rinsed (removal of contaminations) according to VDI 2035 and should
be filled with the heat exchanger fluid named in the design data sheet to the correct
concentration. Water quality to VDI 2035. Too high a concentration of glycol leads to
reduced performance, too low a concentration of glycol can lead to frost damage.