Commissioning and Maintenance
28 © robatherm
Pos: 44.1 /Überschri ften/__Luftfilt er @ 0\mod_1257341371650 _2008.doc @ 2043 @ 2
Filters
Pos: 44.2 /Inbetri ebnahme und Wartung/_Inbe triebnahme @ 0\mod_12579 29574289_2008.doc @ 2116 @ 3
Commissioning
Pos: 44.3 /Sicher heitshinweise/!Vor sicht_Sicherheitshi nweise beachten_Quer verweis @ 0\mod_125777 7093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 44.4 /Inbetri ebnahme und Wartung/Luftf ilter/Luftfil ter_IBN_Einbau Filter einsätze @ 0\mod_12583 65811110_2008.doc @ 2146 @ 4
Installation of Filter Cartridges
Carefully fix filter elements to the frames with tension springs or anchor wailers
respectively, cartridge filters to be fastened to bayonet joints hand tight.
Do not shut or damage filter cartridges.
Check air proof seating of the filter cartridges in the frame.
Pos: 44.5 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Luftfilter_A TEX @ 0\mod_1258365944257 _2008.doc @ 2147 @
Only use approved filter media with ATEX units.
Pos: 44.6 /Inbetri ebnahme und Wartung/Luftf ilter/Luftfil ter_IBN_Filterüber wachung @ 0\mod_1258366009 246_2008.doc @ 2148 @ 444
Filter Monitoring
In order to check the degree of contamination of the filters (except activated carbon filters),
the fitting of a differential pressure manometer on the access side of the unit is
recommended.
Filter End Resistances
Filter Class Rec. End resistance
G1 - G4
M5 - M6, F7
F8 - F9
E10 - E12, H13
150 Pa
200 Pa
300 Pa
500 Pa
Roll Filter
For roll filters the operating and servicing instructions supplied by the manufacturer must be
followed.
Pos: 44.7 /Inbetri ebnahme und Wartung/_W artung @ 0\mod_125792958525 7_2008.doc @ 2117 @ 3