Commissioning and Maintenance
48 © robatherm
Maintenance
Pos: 62.9 /Inbetri ebnahme und Wartung/W artungsintervall_3Mona te/ATEX monatlic h @ 0\mod_1257930528679_20 08.doc @ 2122 @ 4
Maintenance Interval
Every three months. ATEX units every month.
Pos: 62.10 /Sicher heitshinweise/!Vor sicht_Sicherheits hinweise beachten_ Querverweis @ 0\mod_12577 77093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 62.11 /Sicherheitshinweise/IBN&Wartung/!IBN&Wartung_Rotor-WRG_Vorsic ht @ 0\mod_1258390168851_2 008.doc @ 2181 @
Caution
When current feed is not disconnected at all poles, there is a risk of crushing and scraping
to the limbs through sudden running of the rotor caused by an automatic cleaning run or
automatic re-start after power failure.
Pos: 62.12 /Inbetri ebnahme und Wartung/Entfe uchtungsrotor/ Entfeuchtungsrotor _Wartung @ 0\mod_125844 4066338_2008.doc @ 2195 @ 4
Maintenance Work
The maintenance work must be carried out in line with the instructions of the rotor
manufacturer (ask if required).
Desiccant Rotor HRS – Periodic Maintenance
Check rotor for hygiene, foreign bodies, contamination, damage and corrosion
Check sealing strips for contamination, foreign bodies and contact pressure (see above)
Check drive belt for wear and tension, shorten (see above) or change if necessary
Check rotor for imbalance and lateral trueness
Check bearing for incorrect heating, vibration
or running noises and change if necessary
(no later than the end of the theoretical service life)
Check functioning of rotor control, align sensor if necessary
Desiccant Rotor HRS – Maintenance when necessary
Rectify foreign bodies, contamination, damage and corrosion
Clean body of rotor in line with rotor manufacturer's instructions. Depending on the rotor
type, wet cleaning may lead to the destruction of the rotor!
Clean sealing strips, change if there is abrasion
Adjust contact pressure of sealing strips (see above)
Balance or align rotor
Pos: 62.13 /Inbetri ebnahme und Wartung/Entfe uchtungsrotor/ Entfeuchtungsrotor _Außerbetriebse tzung @ 0\mod_12584446688 01_2008.doc @ 2196 @ 4
Shut Down
If standstill is for a longer period, put the rotor intermittently into operation in line with the
manufacturer’s instructions to maintain self purification of the rotor.