Commissioning and Maintenance
52 © robatherm
Reheating Surface – Periodic Maintenance
Remove inspection cover and cleaning cover of the combustion chamber. Remove all
turbulators and check for general condition. Replace if there is heavy corrosion.
Check drainage device and clean if necessary.
Reheating Surface – Maintenance when necessary
Clean all reheating surface pipes with a stainless steel brush and vacuum the collector.
Burner – Periodic Maintenance
On completion of combustion chamber cleaning, the burner maintenance is to be carried
out in accordance with the instructions of the burner manufacturer (in line with DIN 4755
or DVGW-worksheet G600).
Establish exhaust gas values as per Federal Emissions Protection Act.
A record is to be established of all work and forwarded to the manufacturer automatically.
Check gas pipes, connections and gas control system for leaks and eliminate any leaks
found.
Control and Safety Bodies – Periodic Maintenance
Inspection according to commissioning.
Bypass- and Combustion Chamber Damper – Periodic Maintenance
For maintenance see chapter “dampers”.
Checking of active direction: See commissioning.
In general the chimney sweep is responsible for the maintenance of the exhaust pipe
(chimney).