Introduction
2 © robatherm
Pos: 7.10 /Einleitu ng/Brandschutz @ 2\mod_13 34559332779_2008. doc @ 22440 @ 4
Fire Protection
Possible spreading of fire between supply- and exhaust air sections of the AHU (e.g. via the
heat recovery system or recirculating air) must be prevented by appropriate precautionary
measures in the building site’s system (e.g. fire dampers) by others.
A possibly required down gradient grid, according to DIN EN 1886 and AHU-Guideline 01,
must be installed within the system to prevent any carry-over of flammable parts from filters,
mist eliminators or contact humidifiers into the supply air duct.
Pos: 7.11 /Einleitu ng/Übergabe @ 2\mod_1334559 030399_2008.doc @ 22410 @ 4
Handover
AHUs with integrated control technology may only be taken into operation after to
robatherm’s initial commissioning and after handover and customer’s briefing has been
concluded.
Pos: 7.12 /Einleitu ng/Einfriersc hutz @ 2\mod_1334559151487_2 008.doc @ 22425 @ 4
Freeze Protection
In case of ambient temperatures below the freezing point, it can make sense not to switch
down the unit, e.g. in order to prevent dampers from freezing or to avoid any failures during a
later restart.