Commissioning and Maintenance
© robatherm 67
Characteristic Release and Application Pressure
A Release pressure (Pa)
B Number of weight plates (pcs)
C a-distances (mm)
Pos: 72.8 /Inbetri ebnahme und Wartung/_W artung @ 0\mod_125792958525 7_2008.doc @ 2117 @ 3
Maintenance
Pos: 72.9 /Inbetri ebnahme und Wartung/W artungsintervall_1Jahr /ATEX monatlich @ 0\ mod_1258478957281_2008. doc @ 2243 @ 4
Maintenance Interval
Every year. ATEX units every month.
Pos: 72.10 /Sicher heitshinweise/!Vor sicht_Sicherheits hinweise beachten_ Querverweis @ 0\mod_12577 77093652_2008.doc @ 2112 @
Caution
Observe general safety instructions on page 3!
Pos: 72.11 /Inbetri ebnahme und Wartung/Über druckklappe/Über druckklappe_Wartung @ 0\ mod_1258478999684_20 08.doc @ 2244 @
Pressure Relief Damper – Periodic Maintenance
Check pressure relief damper for function, foreign bodies, contamination, damage and
corrosion
Treat all moving parts with lubricating and preserving spray
Treat sealing with Vaseline
Check release pressure, adjust if necessary.
Pressure Relief Damper – Maintenance when necessary
Clean pressure relief damper and rectify any damage and corrosion
Clean with a wet cloth, use grease or oil dissolving agents if necessary
Pos: 73 /Layout/Seite numbruch @ 0\mod_12566286 15637_0.doc @ 2284 @