Commissioning and Maintenance
© robatherm 69
Pos: 74.11 /Inbetri ebnahme und Wartung/MSR- Technik/MSR-Techni k_Wartung @ 0\mod_12585 40543637_2008.doc @ 2247 @
Switch Cabinets, Control Panels, controls – Periodic Maintenance
Check for proper and functionally correct installation and ambient conditions
Check for contamination, corrosion and damage
Check protective coverings are complete
Check electrical/mechanical function of the connections, especially protective conductors
Check functional elements (e.g. operating - and display devices)
Check input signals (e.g. sensor, reference variable) match with rated value
Check optical and acoustic control devices
Check contactors and relays for wear and damage (e.g. contact erosion)
Check switching and control processes (e.g. anti-freeze function)
Check safety devices (e.g. thermal trips)
Check setting of switch cabinet components (e.g. time relays)
Check manual, automatic and remote control functions
Change switch cabinet filter
Switch Cabinets, Control Panels, Controls – Maintenance as required
Clean to maintain functioning
Set, adjust, tighten functional elements (e.g. operating and display devices)
Compensate signals
Readjust
Transducers, Safety and Monitoring Equipment, – Periodic Maintenance
Check for proper and functionally correct installation and ambient conditions
Check for contamination, corrosion and damage
Check electrical/mechanical function of the connections, especially protective conductors
Measure and record measurable quantities at measurement point
Check electrical, electronic and pneumatic measurement signals
Transducers, Safety and Monitoring Equipment – Maintenance as required
Clean to maintain functioning
Readjust, regenerate
Pos: 74.12 /Inbetri ebnahme und Wartung/MSR- Technik/MSR-Techni k_Wartung_Regler und Zusatzmodul @ 0\mod_125854 1799396_2008.doc @ 2249 @
Controllers and Supplementary Modules – Periodic Maintenance
Check for proper and functionally correct installation and ambient conditions
Check for contamination, corrosion and damage
Check natural voltage (e.g. buffer batteries, storage batteries)
Check electrical/mechanical function of the connections, especially protective conductors
Check functional elements (e.g. operating - and display devices)
Check electrical, electronic and pneumatic input signals (e.g. sensors, remote adjustment
devices, reference variables)
Check controller functioning and actuating signal
Check control loop as per setting parameters including all supplementary functions
Controllers and Supplementary Modules – Maintenance when necessary
Exchange storage batteries
Clean to maintain functioning
Set, adjust, tighten functional elements (e.g. operating and display devices)
Compensate signals
Adjust controller functioning and actuating signal
Adjust control loop as per setting parameters including all supplementary functions

Related product manuals