60 Rockwell Automation Publication 856T-UM001B-EN-P - April 2021
Appendix C Device Parameters
Cycle counter-Life time
(Circuit 6)
0X014B/331 0x0006/6 Read-only 0 0…4,294,967,296
UIntegerT
(bit length = 32,
bit offset = 32)
Cycle counter-Life time
(Circuit 7)
0X014B/331 0x0007/7 Read-only 0 0…4,294,967,296
UIntegerT
(bit length = 32,
bit offset = 0)
Alarm Status
Alarm status 0x0135/309
—
Read-only
—0…4095
RecordT
(bit length = 16)
0x0001/1 FALSE=0
Bit 0- Short Circuit
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 0)
0x0002/2 FALSE=0
Bit 1- Open Circuit
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 1)
0x0003/3 FALSE=0
Bit 2 -Class A Over Voltage
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 2)
0x0004/4 FALSE=0
Bit 3- Class A Under Voltage
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 3)
0x0005/5 FALSE=0
Bit 4 -Module Excessive Vibration
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 4)
0x0006/6 FALSE=0
Bit 5 -Device Over Temperature
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 5)
0x0007/7 FALSE=0
Bit 6 -Device Under Temperature
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 6)
0x0008/8 FALSE=0
Bit 7 -ICP Communication Fault
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 7)
0x0009/9 FALSE=0
Bit 8 -Invalid Configuration
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 8)
0x000A/10 FALSE=0
Bit 9 -Class B Over Voltage
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 9)
0x000B/11 FALSE=0
Bit 10-Class B Under Voltage
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 10)
0x000C/12 FALSE=0
Bit 11- Power On Self-Test Failure
(TRUE=Bit=1) / (FALSE= Bit=0)
BOOL
(bit length = 1,
bit offset = 11)
Measurements
Class-A (Voltage) 0x0148/328 — Read-only — 15,000…32,000
UIntegerT
(bit length = 16)
Class-B (Voltage) 0x0149/329 — Read-only — 15,000…32,000
UIntegerT
(bit length = 16)
Actual internal
temperature (°C)
0x005A/90 — Read-only — -40…+95
IntegerT
(bit length = 8)
Min Temperature since
power up (°C)
0x0147/327 — Read-only — -40…+95
IntegerT
(bit length = 8)
Max Temperature since
power up (°C)
0x0146/326 — Read-only — -40…+95
IntegerT
(bit length = 8)
Calibration status 0x0134/308 — Read-only 0
0- Not calibrated
1- Calibration in progress
2-Calibration complete
UIntegerT
(bit length = 2)
Average vibration 0x0142/322 — Read-only — 0…16,000
RecordT
(bit length = 48)
Table 14 - Observation Tab (Continued)
Parameter Name
Index
(Hex/Dec)
Sub Index
(Hex/Dec)
Access Default Value Allowed Value
Data Type
(Length, Offset)