EasyManua.ls Logo

Rockwell Automation Allen-Bradley ControlLogix B Series

Rockwell Automation Allen-Bradley ControlLogix B Series
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24 Rockwell Automation Publication 1756-UM542A-EN-P - September 2014
Chapter 4 Time Synchronization
If you enable CIP Sync on a 1756-EN2T/1756-EN2TR module, the module
looks for other 1588 PTP devices and syncs to the device that has the highest-
quality clock.
The 1756-EN2T/1756-EN2TR modules are boundary clocks that can be a slave
clock on one interface, and a master clock on another interface. The modules can
act as a transparent gateway when a Logix5000 controller uses the time
Grandmaster (the 1756HP-TIME module) on the network. The 1756-EN2T/
1756-EN2TR module must have CIP Sync and Motion enabled. See
Configure
the Ethernet Module/Controller PTP/CIP Sync Settings on page 24.
Configure the Ethernet Module/Controller PTP/CIP Sync Settings
Follow these steps to configure the PTP/CIP Sync settings of the 1756-EN2T/
1756-EN2TR module and controller.
1. Op
en the AOP for the Ethernet module.
2. From the General tab, under Module Definition, click Change.
IMPORTANT
1588 PTP uses a multicast address; therefore, set the switches to allow
multicast, or have IGMP enabled.
IMPORTANT
There is no direct communication between the 1756HP-TIME module Ethernet
ports and a Logix5000 controller. If the 1756HP-TIME module resides in a
remote Logix rack, it needs to communicate through an EN2T(R) module in the
same rack.
IMPORTANT
Most devices supporting 1588 PTP defaults to PTP Enabled: FALSE.
PTP must be enabled on the devices before time synchronization can begin.

Table of Contents

Related product manuals