46 Rockwell Automation Publication 843ES-UM001A-EN-P - February 2020
Chapter 4 Add Device to an EtherNet/IP Network
Disable Explicit Protected Mode
To disable Explicit Protected mode, follow these steps:
1. Set the rotary switches on position 000.
2. Power up the device, and wait for the Module Status indicator to blink red,
the Network Status indicator to turn off, and the Link Status indicator to
turn off.
3. Power down the device.
4. Set the switches for normal operation.
5. Power up the device.
6. The device is now in Explicit Protected mode.