Rockwell Automation Publication 843ES-UM001A-EN-P - February 2020 77
Diagnostics and Troubleshooting Chapter 6
Errors
The following error messages stem from the Studio 5000® environment.
Table 27 - Encoder Error Table (Attribute 135)
(1)
(1) In the Safety Position Sensor Object, no errors can be defined. The device goes to a safe state as it is detecting an error and no longer
communicates.
Fault
Header
[byte]
Bit Description FALSE (0) TRUE (1)
0 0 Reserved - -
1 Operating temperature of the encoder outside the permissible range Ok ERROR
2 Permissible internal light-emitting diode (LED) current in the sensors
exceeded
Ok ERROR
3 Supply voltage outside the permissible range Ok ERROR
4 Maximum velocity has been exceeded Ok ERROR
5 Position error: internal interface Ok ERROR
6 Position error: absolute data error Ok ERROR
7 Position error: configuration error Ok ERROR
1 8 Position error: synchronization error Ok ERROR
9 Position error: error in sensor Ok ERROR
10…15 Reserved - -
21617Reserved - -
18 Memory error: internal interface Ok ERROR
19…23 Reserved - -
Table 28 - Error Messages
Error Code Message Possible Cause
16#0108 Connection-request error
connection type (multi-cast/
uni-cast) not supported.
Check whether the configuration assembly (instance 100 of the Assembly Object) is activated. If yes, check whether the
configuration data are correctly and fully configured in this assembly (see Edit 843ES CIP Safety Encoder Configuration
Categories on page 65).
16#0111 Requested Packet Interval (RPI)
out of range
Make sure that RPI for Safety Connection is in the appropriate range (6…500 ms) and the Standard Connection is in the
appropriate range (1…750 ms). Check that Safety Task RPI is 6 ms or greater.
16#0114 Electronic keying mismatched:
electronic keying product code
and/or vendor ID mismatched.
Wrong device selected, or incorrect major/minor firmware revision selection based on the real device. For example, single-
turn selected instead of multi-turn, or vice versa.
16#0127 Connection request error:
invalid output size.
Check whether the correct communication format for the control system is used. The default value in the control system is
“Data-DINT.” The encoder requires the communication format: “Input Data-DINT.”
16#0204 Connection request error:
connection timeout.
Check the supply voltage on the encoder.
Check the Ethernet cables for the encoder for open circuit.
Check whether the IP address of the encoder matches the IP address that is saved in the control system. Possible causes:
The address switches are not engaged correctly.
The encoder has lost the IP address that is assigned to it after switching back on.
16#fd1f Bad Safety Protocol Format An error occurred while trying to add the Safety Network Segment to a route in Logix. Check Safety Network Number on
Safety Page, refresh Safety Network Number if needed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley Guardmaster CIP and is the answer not in the manual?

Rockwell Automation Allen-Bradley Guardmaster CIP Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley Guardmaster CIP
CategoryMedia Converter
LanguageEnglish

Related product manuals