Programming and Parameters Chapter 2
390 SL MultErr Cnfg
Enter a value to configure the Drive Module's response to a SynchLink Multiplier error. Refer to Par 927 [SL Mult
State] for possible causes for multiplier errors.
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to
this event.
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in
response to this event.
Default
Options:
2 =
0 =
1 =
2 =
3 =
4 =
“FltCoastStop”
“Ignore
“Al arm
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp
391 DPI CommLoss Cfg
Enter a value to configure the drive's response to the failure of a DPI port.
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to
this event.
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in
response to this event.
Default
Options:
2 =
0 =
1 =
2 =
3 =
4 =
“FltCoastStop”
“Ignore
“Al arm
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp
392 NetLoss DPI Cnfg
Enter a value to configure the drive's response to a communication fault from a network card at a DPI port.
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to
this event.
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in
response to this event.
Default
Options:
2 =
0 =
1 =
2 =
3 =
4 =
“FltCoastStop”
“Ignore
“Al arm
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp
393 BusUndervoltCnfg
Enter a value to configure the drive's response to the DC Bus voltage falling below the minimum value.
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
3 - Flt RampStop configures the drive to perform a ramp stop and set the appropriate fault bit, in response to
this event.
4 - FltCurLimStp configures the drive to perform a current-limit stop and set the appropriate fault bit, in
response to this event.
Default
Options:
1 =
0 =
1 =
2 =
3 =
4 =
“Al arm
“Ignore
“Al arm
“FltCoastStop”
“Flt RampStop”
“FltCurLimStp
394 VoltFdbkLossCnfg
Enter a value to configure the drive's response to a communication error between Motor Control (MC) and the
motor voltage feedback board.
0 - Ignore configures the drive to continue running, as normal, when this event occurs.
1 - Alarm configures the drive to continue running and set the appropriate alarm bit when this event occurs.
2 - FltCoastStop configures the drive to perform a coast stop and set the appropriate fault bit, in response to
this event.
Default:
Options:
2 =
0 =
1 =
2 =
“FltCoastStop”
“Ignore
“Al arm
“FltCoastStop”
No. Name
Description
Values
Linkable
Read-Write
Data Type
ATTENTION: Risk of injury or equipment damage exists. Par 390 [SL MultErr Cnfg] lets you determine the action of the drive
if communications are disrupted. By default this parameter causes the drive fault and coast to a stop. You can set this
parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does
not create hazards of injury or equipment damage.
ATTENTION: Risk of injury or equipment damage exists. Par 391 [DPI CommLoss Cfg] lets you determine the action of the
drive if communications are disrupted. By default this parameter causes the drive fault and coast to a stop. You can set this
parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does
not create hazards of injury or equipment damage.
ATTENTION: Risk of injury or equipment damage exists. Par 392 [NetLoss DPI Cnfg] lets you determine the action of the
drive if communications are disrupted. By default this parameter causes the drive fault and coast to a stop. You can set this
parameter so that the drive continues to run. Precautions should be taken to ensure that the setting of this parameter does
not create hazards of injury or equipment damage.

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 700S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 700S and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 700S Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 700S
CategoryController
LanguageEnglish

Related product manuals