78 Rockwell Automation Publication 20D-PM001D-EN-P - March 2019
Chapter 2 Programming and Parameters
No. Name
Description
Values
Linkable
Read-Write
Data Type
412 Power EE TP Sel
Enter or write a value to select drive power EEPROM data displayed in Par 413 [Power EE TP Data]. The default is 0 “Zero”.
Note: Options 74 - 92 were changed and options 93 - 111 were added for firmware version 3.001.
413 Power EE TP Data
Displays the data selected by Par 412 [Power EE TP Sel].
Default:
Min/Max:
0
-/+2200000000
RO Real
414 Brake/Bus Cnfg
Configures the brake and bus operation of the drive.
• Set bit 0 “Brake Enable” to enable the operation of the internal brake transistor.
• Set bit 1 “Brake Extern” to configure the brake to use an external resistor.
• Set bit 2 “Bus Ref High” to select the “high” voltage setting as the turn-on point for the Bus Voltage Regulator. With the “high” setting brake operation starts when bus voltage reaches the value
of Par
415 [BusReg/Brake Ref], and Bus Voltage Regulator operation starts when bus voltage reaches the value of Par 415 [BusReg/Brake Ref] plus 4.5%. With the “low” setting, the bus
regulator turns on first at the value set by Par 415 [BusReg/Brake Ref] and then the dynamic braking turns on when there are any transients above the value set in Par 415 [BusReg/Brake Ref].
• Set bit 3 “Bus Reg En” to enable the Bus Voltage Regulator. The output of the Bus Voltage Regulator is summed with Par
128 [Regen Power Lim] and fed into the Power Limit Calculator. It, in
effect, reduces regenerative torque references when the bus voltage is too high.
Notes: This parameter was changed to non-linkable and bits 5 and 6 were added for future use - not active for use with firmware version 3.001. Remove bits 5 and 6 for firmware version 4.001 - not
used.
415 BusReg/Brake Ref
Sets the “turn-on” voltage for the bus regulator and brakes. Enter a percentage of the high voltage setting for
the voltage class. For example, on a 400…480V AC drive,
Note: The minimum value for frame 5 and up, 600V AC input drives was changed from 110.5000 to 100.0000
for firmware version 4.002.
(1) The minimum value is 100.0000 for frame 5 and up, 600V AC input drives.
Default:
Min/Max:
Units:
111.0000
110.5000
(1)
/117.8000
%
RW Real
416 Brake PulseWatts
Limits the power delivered to the external Dynamic Brake (DB) resistor for one second, without exceeding the
rated element temperature. You may change the value of this parameter only if you have selected an external
DB resistor (set bit 1 “Brake Extern” of Par
414 [Brake/Bus Cnfg]. If this rating is not available from the resistor
vendor, you can approximate it with this equation: Par
416 [Brake PulseWatts] = 75,000 x Weight, where
Weight equals the weight of resistor wire element in pounds (not the entire weight of the resistor). Another
equation you can use is: Par 416 [Brake PulseWatts] = Time Constant x Brake Watts; where Time Constant
equals the amount of time to reach 63% of its rated temperature while the maximum power is applied, and
Brake Watts is the peak power rating of the resistor.
Note: The maximum value was changed from 1000000.0000 to 1000000000.0000 for firmware version 3.001.
Default:
Min/Max:
Units:
2000.0000
1.0000/1000000000.0000
W
RW Real
Options:
0 = Zero 19 = Bus VltScale 38 = IGBT Rated A 61 = Convt Type 80 = HH1 P/B ID 99 = HH2 P/B ID
1 = Volt Class 20 = Sml PS Watts 39 = IGBT V Thres 62 = DC Bus Induc 81 = HH1 S/W ID 100 = HH2 S/W ID
2 = Assy Rev 21 = Sml PS Min V 40 = IGBT Slope R 63 = AC Inp Induc 82 = HH1 P/B Rev 101 = HH2 P/B Rev
3 = ASA S/N 22 = Lrg PS Watts 41 = IGBT Sw Engy 64 = Precharg Res 83 = HH1 S/W Rev 102 = HH2 S/W Rev
4 = Manuf Year 23 = Lrg PS Min V 44 = IGBT CS Tres 65 = PrechThrm Tc 84 = HH1 Extr Data 103 = HH2 ExtrData
5 = Manuf Month 24 = Inv Rated Kw 45 = IGBT CS Tc 66 = Mtr NP Units 85 = HH1 VoltIndx 104 = HH2 VoltIndx
6 = Manuf Day 25 = Inv Rated V 46 = Diode V Thrs 67 = Mtr NP Power 86 = HH1 SizeIndx 105 = HH2 SizeIndx
7 = Tst ProcStat 26 = Inv Rated A 47 = Diode SlopeR 68 = Mtr NP Volts 87 = HH1 Option 106 = HH2 Option
8 = Life PwrCycl 27 = Inv 1min Amp 48 = Diode JC Tr 69 = Mtr NP Amps 88 = HH1 HrdPrdct 107 = HH2 HrdPrdct
9 = Life Pwrup 28 = inv 3sec Amp 49 = Diode JC Tc 70 = Mtr NP Freq 89 = HH1 H/W Mdfy 108 = HH2 H/W Mdfy
10 = Life RunTime 29 = SW OverC Amp 50 = GBT Tjmax 71 = Mtr NP RPM 90 = HH1 1V/Amp 109 = HH2 1V/Amp
11 = Kw Accum 30 = DC Bus Cap 51 = HS Max DegC 72 = Mtr IR Vdrop 91 = HH1 2s/Amp 110 = HH2 2s/Amp
12 = Mw Hrs Accum 31 = Min PWM Khz 52 = DB IGBT Amp 73 = Mtr Id Ref 92 = HH1 Scale 111 = HH2 Scale
13 = Inv High Vlt 32 = Max PWM Khz 53 = DB ohms 74 = HH1 Data Rev 93 = HH2 Data Rev
14 = Reserved 33 = Dfl PWM Khz 54 = DB E Jo/degC 75 = HH1 Dev Type 94 = HH2 Dev Type
15 = Fan/Pwr Cntl 34 = PWM Dead us 55 = DB EB C/Watt 76 = HH1 Serial # 95 = HH2 Serial #
16 = Temp Sensor 35 = Drive Frame 56 = DB B Jo/degC 77 = HH1 Test Date 96 = HH2 TestDate
17 = Phs AmpScale 36 = IGBTs per Pk 57 = DB BA C/Watt 78 = HH1 Vcn Code 97 = HH2 Vcn Code
18 = Gnd AmpScale 37 = GBT Rated V 60 = DB Ambt Tmax 79 = HH1 CrsCncID 98 = HH2 CrsCncID
Options
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Bus Reg En
Bus Ref High
Brake Extern
Brake Enable
Default xxxxxxxxxxxx1100
Bit 1514131211109876543210
0 = False
1 = True