PowerFlex Digital DC Drive User Manual - Publication 20P-UM001C-EN-P - July 2008
Programming and Parameters 3-59
COMMUNICATIONS
Masks & Owners
599 [Local Mask]
Controls which adapters are allowed to take exclusive control
of drive logic commands (except stop). Exclusive “local”
control can only be taken while the drive is stopped.
See [Logic Mask]
600 [Stop Owner]
The adapters that are presently issuing a valid stop command. 0 = No Command, 1 = Issuing Command, x = Reserved.
601 [Start Owner]
The adapters that are presently issuing a valid start
command.
See [Stop Owner]
602 [Jog Owner]
The adapters that are presently issuing a valid jog command.
See [Stop Owner]
603 [Direction Owner]
The adapter that currently has exclusive control of direction
changes.
See [Stop Owner]
604 [Reference Owner]
The adapter that has the exclusive control of the command
frequency source selection.
See [Stop Owner]
605 [Accel Owner]
The adapter that has exclusive control of the acceleration
ramp rate (Pars 660 [Accel Time 1] and 24 [Accel Time 2]) for
the drive.
See [Stop Owner] 24,
660
606 [Fault Clr Owner]
Adapter that is presently clearing a fault.
See [Stop Owner]
607 [MOP Owner]
Adapters that are currently issuing increases or decreases in
MOP command frequency.
See [Stop Owner]
608 [Local Owner]
Adapter that has requested exclusive control of all drive logic
functions. If an adapter is in local lockout, all other functions
(except stop) on all other adapters are locked out and non–
functional. Local control can only be obtained when the drive
is not running.
See [Stop Owner]
609 [Decel Owner]
The adapter that has exclusive control of the deceleration
ramp rate (Pars 662 [Decel Time 1] and 32 [Decel Time 2])
for the drive.
See [Stop Owner]
32,
662
631 [Decel Mask]
Controls which adapters can select the deceleration ramp
rate (Pars 662 [Decel Time 1] and 32 [Decel Time 2]) of the
drive.
See [Logic Mask]
32,
662
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Digital In
Default
xxxxxxxxxx000000
Bit
1514131211109876543210