3-46 Programming and Parameters
Utility File
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
UTILITY
Reference Config
209 [Save HIM Ref]
Enables a feature to save the present reference value issued by the HIM to drive memory when a power loss occurs. The
value is restored to the HIM at power up.
Bit 0 - “At Pwr Down” 0 = Do not save, 1 = Save at power down
210 [Man Ref Preload]
Enables/disables a feature to automatically load the present “Auto”
frequency reference value into the HIM when “Manual” is selected.
Allows smooth speed transition from “Auto” to “Manual.
Default:
Options:
1 =
0 =
1 =
“Enabled”
“Disabled”
“Enabled”
249 [Save MOP Ref]
Enables/Disables the feature that saves the present MOP frequency reference at power down or at stop.
Note: This parameter can be assigned to a digital input.
Bit 0 “At Pwr Down” - When set to “0” = Do not save, “1” = Save
Bit 1 “At Stop” - When set to “0” = Do not save, “1” = Save
1322 [Direction Mode]
Selects the method that will be used for changing direction.
“Unipolar” - Drive Logic determines the direction.
“Bipolar” - The sign of the reference determines the direction.
“Rev Disable” - Forward direction only (not changeable).
Default:
Options:
0 =
0 =
1 =
2 =
“Unipolar”
“Unipolar”
“Bipolar”
“Rev Disable”
1375 [MOP Select]
Selects the destination of the MOP signal.
Default:
Options:
0 =
0 =
1 =
2 =
3 =
4 =
“Off
”Off
“Speed Ref A”
“Speed Ref B”
“Trim Speed”
“TB Man Ref
Drive Memory
211 [Param Access Lvl]
Selects the parameter display level.
“Basic” = Reduced parameter set.
“Advanced” = Full parameter set.
Default:
Options:
0 =
0 =
1 =
“Basic”
“Basic”
“Advanced”
258 [Reset Defaults]
Setting this parameter to 1 “Factory” will load the default settings in
the drive firmware.
Default:
Options:
0 =
0 =
1 =
“Ready”
“Ready”
“Factory”
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
At Pwr Down
Default
xxxxxxxxxxxxxxx1
Bit
1514131211109876543210
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
At Stop
At Pwr Down
Default
xxxxxxxxxxxxxx00
Bit
1514131211109876543210