EasyManua.ls Logo

Rockwell Automation PowerFlex series - Drive Status

Rockwell Automation PowerFlex series
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PowerFlex Digital DC Drive User Manual - Publication 20P-UM001C-EN-P - July 2008
4-2 Troubleshooting
Drive Status
The condition or state of your drive is constantly monitored. Any changes
will be indicated through the LEDs and/or the HIM (if present).
Figure 4.1 Drive Status Indicators
# Name Color State Description
STS
(Status)
Green Flashing Drive ready, but not running and no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing,
Drive Stopped
A condition exists that is preventing the drive from
starting. Check parameters 1403
[Start Inhibits] and/or
1380
[Drive Alarm 1].
Flashing,
Drive Running
An intermittent type 1 alarm condition is occurring.
Check parameter 1380
[Drive Alarm 1]. Refer to Fault
Descriptions on page 4-4 and/or Alarm Descriptions on
page 4-7.
Steady,
Drive Running
A continuous type 1 alarm condition exists. Check
parameter 1380
[Drive Alarm 1]. Refer to Fault
Descriptions on page 4-4 and/or Alarm Descriptions on
page 4-7.
Red Flashing A fault has occurred. Check [Fault x Code] or view the
Fault Queue on the HIM. Refer to Fault Descriptions on
page 4-4.
Steady A non-resettable, non-configurable fault has occurred.
Check [Fault x Code] or view the Fault Queue on the
HIM. Refer to Fault Descriptions on page 4-4
.
PORT Refer to the Communication
Adapter User Manual.
Status of DPI port internal communications (if present).
MOD Status of communications module (when installed).
NET A Status of network (if connected).
NET B Status of secondary network (if connected).
STS
PORT
MOD
NET A
NET B

Table of Contents