PowerFlex Digital DC Drive User Manual - Publication 20P-UM001C-EN-P - July 2008
Troubleshooting 4-9
Fld Current
Loss
The field current is too low. Refer to the “Fld Current Loss” fault description on
page 4-4
for more information.
Motor Over
Te mp
The motor has exceeded its temperature rating (as signaled by the thermistor
connected to the drive terminals 78 and 79). Refer to the “Motor Over Temp”
fault description on page 4-5
for more information.
Start At
PowerUp
Par 1344 [Start At Powerup] is enabled. The drive may start at any time after
drive power up and the time specified in Par 1345
[Powerup Delay] has
elapsed.