EasyManua.ls Logo

Rockwell Automation PowerFlex series - Page 215

Rockwell Automation PowerFlex series
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PowerFlex Digital DC Drive User Manual - Publication 20P-UM001C-EN-P - July 2008
Application Notes C-19
Enter the step value in Par 60 [TstGen Amplitude], so that the speed
remains inside the range to be tuned.
The optimization is carried out separately for each range and the
parameters of the regulator are set for each range with Pars
[Adaptive P Gainx] and [Adaptive I Gainx].
After the optimization of the different phases review the entire
speed range. By changing the value of [Adaptive Joint x] it is
possible to reduce the instabilities present in the transients during
the changes from one range to the other. Increasing the values
transients are slighter.
When Par 182 [Adaptive Reg Typ] = 1 “Adaptive Ref”, tuning is
application specific.
When the speed zero logic (see page C-22
) is disabled (factory default
setting) and the drive is disabled, the gains of the speed regulator are
active. These are set via Pars 188 [Adaptive P Gain1] and 189 [Adaptive
I Gain1]. When the speed zero logic is enabled, the values set when the
motor is stopped are valid.

Table of Contents

Related product manuals